Operating Instructions
28
4.5 Current Plus Monitoring
The Liebert RDC has a Current Plus Monitoring (CPM) feature that monitors the current and voltage
of the panelboard main circuit breaker. The CPM includes a monochrome Liquid Crystal Display
(LCD) with oval bezel that includes power and alarm LEDs, audible alarm and silence push button.
The CPM displays the power parameters and alarms listed below for each panelboard main. The dis-
play is mounted on the front and rear doors. The display and switches are accessible without opening
the door.
The CPM displays circuit identification, the status of each breaker and the following parameters:
Voltage - Line-to-Line
Voltage - Line-to-Neutral
Neutral Current
Ground Current
kVA
Power Factor
Voltage Total Harmonic Distortion (THD)
Current Total Harmonic Distortion (THD)
Crest Factor
The CPM annunciates alarm messages for the following conditions. Alarm thresholds for monitored
parameters are adjustable through the service port to match site requirements. The alarms and their
factory setpoints for the alarms are:
Summary Alarm - detects and annunciates upon occurrence of any alarm.
Summary Alarm Contacts - The CPM has two Form C (1 NO and 1 NC) summary alarm contacts
for remote alarm status—one contact per panelboard. The contacts are rated at 24VAC @ 1A. The con-
tacts change state when any alarm or warning occurs and reset when the alarm is cleared.
To facilitate troubleshooting, all alarms are stored in non-volatile memory to protect against erasure
by a power outage. Alarms must be manually reset after alarm conditions are corrected. Alarms may
be reset through Modbus.
An event log saves details of up to 128 alarms using a first-in, first-out (FIFO) storage method.
Communication - A two-wire multidrop RS485 Modbus port is available for connections to a
Building Management System (BMS) or Liebert SiteScan Monitoring Interface. See Figure 23 for
connection details.
Alarm Default Setpoint
Overvoltage A line-to-line voltage exceeds +6% of nominal
Undervoltage A line-to-line or line-to-neutral voltage falls below -13% of nominal
Neutral Overcurrent Current exceeds 95% of breaker amps
Ground Overcurrent Current exceeds 5 amps
Phase Overcurrent Warning Current exceeds 75% of breaker amps
Phase Overcurrent Current exceeds 80% of breaker amps
Summary Alarm