ControlWave Gas Flow Computer (GFC Plus) Instruction Manual (CI-ControlWave GFC Plus)
Revised Feb-2013 Operation 4-3
4.2.2 Changing Port Settings
You change port settings (baud rate, port type, IP address, and so on)
using the Flash Configuration utility.
You must establish communications with the ControlWave deviceusing
NetView, LocalView, or TechView before you can run the Flash
Configuration utility.
Note: For detailed information on using the Flash Configuration utility,
see Chapter 5 of the OpenBSI Utilities Manual (D5081).
Caution
When you change the baud rate for a port, the baud rate changes as
soon as you write the flash file changes to the RTU, and do not require
a reset. For this reason, you should not change baud rate for the active
port on which you are communicating, or communications will
immediately stop due to the baud rate mismatch between the PC port
and the controller port. If this happens accidentally, you can use CPU
switch settings as discussed in the notes in Section 4.2.1 to restore
defaults and re-establish communications.
4.2.3 Collecting Data from the ControlWave GFC Plus
OpenBSI utilities such as DataView, Data Array Save/Restore and
Harvester allow you to collect real time data (values of variables, array
values, alarm messages) and historical data (audit records, archive files)
from the ControlWave. See the OpenBSI Utilities Manual (D5081) for
details. SCADA software such as OpenEnterprise can then present this
data to an operator in the form of graphical displays and reports.
4.3 Creating and Downloading an Application (ControlWave Project)
Most GFC Plus users purchase the ControlWave gas flow measurement
application (ControlWave project) which ships pre-installed in the GFC
Plus when it leaves the factory.
You can, however, create your own project using PC-based
ControlWave Designer software. Instructions for creating a
ControlWave project are beyond the scope of this manual. Please refer
to the following sources for information:
Getting Started with ControlWave Designer (D5085)
ControlWave Designer Programmer’s Handbook (D5125)
ControlWave Designer online help
You must connect the GFC Plus to a PC running ControlWave Designer
software and OpenBSI software.
Note: You can download an application either from ControlWave
Designer or from the OpenBSI 1131 Downloader.