ControlWave Gas Flow Computer (GFC Plus) Instruction Manual (CI-ControlWave GFC Plus)
2-26 Installation Revised Feb-2013
Like the power distribution board and the digital to relay I/O board,
each ControlWave Loop Supply board mounts to the inside of the
enclosure using a Snap Track that you secure to a dual PCB mounting
bracket.
2.9 Communication Connections
Communication is via the serial ports and optional Ethernet port.
2.9.1 Connections to RS-232 Serial Port(s) on the CPU/System
Controller Board
An RS-232 port provides point-to-point, half-duplex and full-duplex
communications (for a maximum of 20 feet using data quality cable).
Your CPU includes two RS-232 ports (COM1 and COM2) as well as
one port (COM3) configurable for either RS-232 or RS-485 operation.
COM1 provides a choice of connectors based on a jumper setting. It is
factory-connected to the local port at the bottom of the unit’s cover.
Figure 2-15 shows the local port cable connections for COM1.
Figure 2-15. PC Connected to ControlWave GFC Plus via Circular Local Port