ASCO 5350 Installation Manual
381333-315 D ASCO Power Technologies Page 11
Troubleshooting
Number Symptom Probable Cause Recommended Action
1 Power ON light is off
The DC or AC power source is
inadequate or off.
Restore the DC or AC power supply.
Check the terminals, fuse, circuit breaker.
2
Lamp test button does not
work.
Alarm silence does not
respond.
There is no response on any
key.
The Control switch is locked. Insert Control key and turn it to unlock.
3 The power ON light is blinking.
The unit keeps on resetting due
to watchdog-reset possibly due
to corruption of software.
Refer to Installation Manual 381333-315.
Try to reprogram the unit with the latest
software.
Contact ASCO Services for replacement.
800-800-ASCO or
4
Transfer button does not work
(load transfer does not occur).
Button not held long enough.
Hold the button for at least 5 seconds
until you hear a beep..
ATS Annunciator could have
changed to default settings.
Refer to Installation Manual 381333-315.
Use the configuration details entered on
page 2; reconfigure the ATS Annunciator.
Password not set
The password must be configured.
See Modbus Notes on page 8.
5 Buzzer is beeping continuously.
Communication with the Power
Manager may have stopped.
Refer to Installation Manual 381333-315.
Check the Ethernet connections:
ATS Annunciator to the LAN and
Power Manager to the LAN.
6
Communication alarm occurs
but all configurations are
correct.
Communication protocol may not
the same as that of the Power
Manager (if present).
Refer to Installation Manual 381333-315.
Verify that the protocol on both devices is
the same.
7
A light does not come on when
a corresponding button is
pressed.
ATS Annunciator is
not functioning properly.
Contact ASCO Services for replacement.
800-800-ASCO or
8
A light does not come on when
the lamp test button is pressed.
ATS Annunciator is
not functioning properly.
Contact ASCO Services for replacement.
800-800-ASCO or