Designing a Liebert XD Solution
21
3.14 Liebert XDC DX R-407c Circuit Volume—Air Cooled Units
Weigh in the calculated charge based on Tables 7, 8 and 9.
3.15 Chilled Water Piping
The XDP is offered only with a two-way chilled water control valve. Some applications may require
the use of a pressure activated bypass valve, to prevent dead-heading of the chilled water pump. This
bypass valve must be specified by the engineer responsible for design of the chilled water field piping
system.
Chilled water connections to the XDP are near the bottom of the unit. Refer to the XDP user manual
(SL-16641) for further information. Piping is routed downward from the unit to chilled water piping
under the raised floor. Connections are made using standard practices for copper chilled water piping.
Victaulic
®
connections may be used to simplify installation in existing facilities. Refer to Table 15 for
additional information.
3.16 Electrical
Make all wiring and electrical connections in accordance with local and national codes. Refer to equip-
ment nameplate regarding wire size and circuit protection requirements. Refer to electrical schematic
when making connections.
Table 7 Indoor unit refrigerant charge—R-407C
Model 60 Hz Charge/Circuit lb. (kg)
XDC160 4.5 (2.0)
Table 8 Outdoor condenser charge—R-407C
Model Charge / Circuit, lb (kg)
CDL830 182 (82.6)
CSL616 254 (115.2)
CSL415 182 (82.6)
Table 9 Liquid line charge - R-407C refrigerant per 100 ft (30 m) of Type “L” copper tube
O.D.,
inches
Liquid Line,
lb (kg)
Hot Gas Line,
lb (kg)
3/8 3.7 (1.7) -
1/2 6.9 (3.1) -
5/8 11.0 (5.0 2.2 (1.0)
3/4 15.7 (7.1) 3.1 (1.4)
7/8 23.0 (10.4) 4.5 (2.0)
1-1/8 39.3 (17.8) 7.8 (3.5)
1-3/8 59.8 (27.1 11.8 (5.4)
1-5/8 - 16.7 (7.6)