Page 1 - Liebert Xtreme Density™

Precision Cooling forBusiness Critical ContinuityLiebert Xtreme Density™System Design Manual

Page 2 -

System Description4Figure 6 Top-mounted XDV modules with flexible piping in hot aisle-cold aisle arrangementHot aisles and cold aisles alternate, taki

Page 3 - TABLE OF CONTENTS

System Description51.4 Liebert XDP—Pumping UnitThe XDP isolates the building’s chilled water circuit from the XD Coolant circuit. The XDP circulates c

Page 4

System Description61.5 Liebert XDC—ChillerThe XDC is an indoor chiller that connects directly to the XDO or XDV units and provides coolant cir-culatio

Page 5

System Description71.7 Liebert XDA—Air Flow EnhancerThe XDA is a fan unit that boosts the airflow through densely populated enclosures, removing hot s

Page 6

Starting a New Equipment Cooling Project82.0 STARTING A NEW EQUIPMENT COOLING PROJECT2.1 Determining Cooling Equipment Needs1. Is there adequate space

Page 7 - 1.0 SYSTEM DESCRIPTION

Starting a New Equipment Cooling Project92.2 Implementing a Hot-Aisle/Cold Aisle DesignA best practice is to use rows of equipment racks in an alterna

Page 8

Designing a Liebert XD Solution103.0 DESIGNING A LIEBERT XD SOLUTIONLiebert XD systems are intended for use with precision air conditioning equipment,

Page 9

Designing a Liebert XD Solution113.3 Selecting Liebert XDO or Liebert XDV ModulesThe next step is to select XDO or XDV cooling modules to be configure

Page 10

Designing a Liebert XD Solution123.5.2 Determining Vertical Placement of Liebert XDOs Above the Cold AisleIn the maximum density configuration, Lieber

Page 11 - 1.4 Liebert XDP—Pumping Unit

Designing a Liebert XD Solution133.6 Liebert XDV Unit PlacementXDV units should be placed on top of the cabinets that generate the greatest amount of

Page 13 - System Description

Designing a Liebert XD Solution143.7 Liebert XDP/XDC PlacementThe XDP/XDC may be placed in the critical space or in an adjacent equipment room. The al

Page 14

Designing a Liebert XD Solution15Figure 15 XDV units mounted on racks emitting 5kW of heat top viewFigure 16 XDV units mounted on racks emitting 8kW o

Page 15

Designing a Liebert XD Solution16Figure 17 XDV units mounted on racks emitting 16kW of heat top viewDownflow Cooling UnitDownflow Cooling UnitPerforat

Page 16

Designing a Liebert XD Solution173.9 Liebert XD Coolant™ The coolant used in the XD system is HFC-134a (1,1,1,2-tetrafluoroethane), made by a number o

Page 17 - 3.5 Liebert XDO Placement

Designing a Liebert XD Solution18The assembly and connection means used for piping in the XD system are similar to that of conven-tional refrigeration

Page 18

Designing a Liebert XD Solution193.12 Bypass Flow ControllersTo ensure the XDP/XDC pumps operate within the optimum range, some installations require

Page 19

Designing a Liebert XD Solution203.13 Determining Coolant VolumeAfter the preliminary system design is completed, Tables 5, through 9 may be used to d

Page 20 - 3.7 Liebert XDP/XDC Placement

Designing a Liebert XD Solution213.14 Liebert XDC DX R-407c Circuit Volume—Air Cooled UnitsWeigh in the calculated charge based on Tables 7, 8 and 9.3

Page 21

XD Overhead Cooling Module—Liebert XDO224.0 XD OVERHEAD COOLING MODULE—LIEBERT XDO Standard Features XDO• Micro Channel Heat Exchanger—The Liebert XDO

Page 22

XD Overhead Cooling Module—Liebert XDO23Figure 23 XDO16 internal mounting location DPN000771Pg. 5 Rev. 37/8" (22mm)diameter mountingholes7/8"

Page 23 - 3.9 Liebert XD Coolant™

iTABLE OF CONTENTS1.0 SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11.1

Page 24 - 3.11 Liebert XD Piping Slope

XD Overhead Cooling Module—Liebert XDO24Figure 24 XDO top and front electrical access points4.1 Liebert XD Vertical Top Cooler (XDV)4.1.1 Standard Fea

Page 25 - 3.12 Bypass Flow Controllers

XD Overhead Cooling Module—Liebert XDO254.1.2 Optional Features Liebert XDV• Factory-Installed Flexible Piping (For use with prefabricated piping asse

Page 26

XD Overhead Cooling Module—Liebert XDO26Figure 26 XDV dimensions with factory-installed flex pipeDepth, Top39-1/2" (1003mm)Width22-7/8" (581

Page 27 - 3.16 Electrical

XD Overhead Cooling Module—Liebert XDO27Figure 27 XDV electrical connectionsRear of XDVRear View of XDVDPN000770, Page 3Rev. 2Right side of XDVCondens

Page 28 - Optional Features XDO

XD Overhead Cooling Module—Liebert XDO28Figure 28 Suspending single XDV from UnistrutsFigure 29 Suspending single XDV from the roof structureUnistrut(

Page 29

XD Overhead Cooling Module—Liebert XDO29Figure 30 Alternative mounting methods—mounting multiple XDV units Unistrut, field-suppliedBolt, 3/8"-16,

Page 30

XD Overhead Cooling Module—Liebert XDO304.2 Liebert XD Piping Dimensions and FeaturesFigure 31 Five-port prefabricated piping for XDV modulesTable 10

Page 31 - Return (Out)

XD Overhead Cooling Module—Liebert XDO31Figure 32 Two-port prefabricated piping for XDV modulesTable 11 Two-port prefabricated piping legendBranch Pip

Page 32

XD Overhead Cooling Module—Liebert XDO324.3 Liebert XDP Standard Features• Heat Exchanger—Brazed plate design with interwoven circuiting constructed o

Page 33

XD Overhead Cooling Module—Liebert XDO33Figure 33 XDP dimensions, access points and external featuresXDO/XDVReturn 2-1/8" dia.ReturnSupplyFrontof

Page 34

iiFIGURESFigure 1 Pressure enthalpy diagram - refrigerant. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 35

XD Overhead Cooling Module—Liebert XDO34Figure 34 Front view of XDP and electrical enclosureFigure 35 XDP electrical enclosure knockout locations for

Page 36 - Rev. 2, Pg. 2

XD Overhead Cooling Module—Liebert XDO35Figure 36 XDP high voltage connectionsCustomer PowerConnectionDisconnectSwitchCircuitBreakerContactorTransform

Page 37 - Rev. 2, Pg. 1

XD Overhead Cooling Module—Liebert XDO364.4 Liebert XDC Standard Features• Compressors—Scroll with a suction gas cooled motor, vibration isolators, th

Page 38

XD Overhead Cooling Module—Liebert XDO37Figure 38 XDC piping locationsFigure 39 Front view of XDC and electrical enclosuresG - Supply to cooling units

Page 39

XD Overhead Cooling Module—Liebert XDO38Figure 40 XDC electrical enclosure knockout locations for field wiring Figure 41 XDC high voltage connections—

Page 40

XD Overhead Cooling Module—Liebert XDO39Figure 42 XDC high voltage connections—secondary disconnect switchFigure 43 XDC heat rejection electrical conn

Page 41

XD Overhead Cooling Module—Liebert XDO40Figure 44 XDC electrical enclosure knockout locations for ELVFigure 45 XDC ELV field connections points

Page 42

Specifications415.0 SPECIFICATIONSTable 12 Liebert XDO specificationsModelsXDO16BK--0, XDO16DK--0(60Hz)XDO16BT--0, XDO16DT--0(60Hz)XDO16BT--0, XDO16DT

Page 43 - Rev. 1, Pg. 3

Specifications42Table 13 Liebert XDC specificationsParameter 60Hz Models 50Hz ModelsCooling Capacity, Nominal46 tons / 160kW with 125ºF (51.6ºC) conde

Page 44

Specifications43Table 14 Liebert XDV specificationsNumber of models 8, based on input voltage, optional condensate sensing and flex hose optionCooling

Page 45 - Electrical handy box

iiiTABLESTable 1 Calculating quantity and spacing of XDO modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Table 2

Page 46

Specifications44Table 15 Liebert XDP specificationsNumber of Models 4, based on input voltage and pump redundancyCooling Capacity, Nominal160 kW / 46

Page 48

Emerson Network Power. The global leader in enabling Business-Critical Continuity.EmersonNetworkPower.comEmerson Network Power and the Emerson Network

Page 50

System Description11.0 SYSTEM DESCRIPTIONThe Liebert XD™ family of cooling units delivers efficient, sensible cooling to high-heat environ-ments. XD s

Page 51

System Description21.1 Direct and Indirect System ConfigurationsLiebert XD systems are available in Direct and Indirect configurations—differentiated

Page 52 - Locations

System Description3Figure 4 Suspended XDO modules in hot aisle-cold aisle arrangement1.3 Liebert XDV—Vertical Above-Cabinet Cooling Module The XDV is