Designing a Liebert XD Solution
19
3.12 Bypass Flow Controllers
To ensure the XDP/XDC pumps operate within the optimum range, some installations require one or
more bypass flow controller(s). These devices are added to the field piping, and simulate the flow of
additional cooling modules.
Each bypass flow controller should be installed with one shutoff valve to allow the controller to be dis-
abled when cooling modules are added to an XD system.
Bypass flow controllers may be placed anywhere in the field piping but should be placed in a conve-
nient, accessible location. See Figures 20 and 21 for piping details of the bypass flow controller.
Refer to Table 4 to determine the number of bypass flow controllers needed, based on the total nomi-
nal cooling capacity of the cooling modules in each XD system.
Figure 20 Bypass flow controller arrangement
Figure 21 Bypass flow controller details, dimensions
Table 4 Bypass flow controllers required in a Liebert XD system
Number of Bypass Flow Controllers
In XDP System In XDC System
XDV Units
16-20 00
12-15 11
8-11 22
4-7 3 Not Recommended
XDO Units
8-10 00
6-7 11
4-5 22
2-3 3 Not Recommended
Return
Main
7/8" Refrigerant Grade
Full Port Ball Valve
Field-Supplied and Field-Installed
Supply
Main
Bypass Flow Controller
(Field-Installed)
Flow Direction
7/8
"
(2.2mm) ID
4
"
(102mm)