Component Operation and Maintenance, Checks and Adjustments
71
13. Replace the canister by reversing the above procedure. Make special note of the following:
Fault Descriptions
Overcurrent—Operating current exceeds present limit
Fill Valve—Continuously energized valve exceeds preset limit
End of Life—Drain count limit exceeded in a 24-hour period
Fail to Make Capacity—Does not reach operational current within initial 24 hours
Test Points
NOTE
When reconnecting the power wiring, follow exactly the instructions included with kit
153315P1 and P2 or the unit electrical schematic with canisters 136799P1 and P2.
When replacing the canister, always check the fill and drain solenoids for proper operation
Table 6 Faults—canister generator humidifier
Priority Name LED Indication Description
1 Over Current Solid Humidifier Lockout
2 Fill Valve 2 second flash Humidifier Lockout
3 End of Life 4 second flash Humidifier Lockout
4 Fail to Make Capacity 1 second flash Indicate only
TP1—Time Cycle Pot 1 VDC = 60 seconds
TP2—Low Drain Pot 3 VDC = 80%
TP3—Capacity Pot 3.5 VDC = 85%
TP5—RT Capacity 1 VDC = 100%