Emerson Liebert CW User Manual Page 22

  • Download
  • Add to my manuals
  • Print
  • Page
    / 88
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 21
Liebert CW Dimensions and Weights
16
Figure 11 Floor stand and floor planning dimensions for downflow models CW051 and CW060 with EC
fans
Point Description X, in (mm) Y, in (mm) Connection Size / Opening, in (mm)
CD
Condensate Drain*
60-7/8 (1547) 27-3/4 (705)
3/4 (19) FPT
W/Optional Condensate Pump** 1/2 (13) Cu Sweat
HUM Humidifier Supply Line 59-1/8 (1502) 28-5/8 (727) 1/4 (6) Cu Sweat
CWP
Chilled Water Piping Slot (Center) 66-9/16 (1691) 31-1/4 (794) 11 x 3 (279 x 76)
Supply & Return Piping Diameter
CW051: 1-5/8 (41)
CW060: 2-1/8 (54)
HV High Volt Electrical Connection 59-3/8 (1509) 30-3/4 (781) 3 (76)
LV Low Volt Electrical Connection 60-7/8 (1547) 29-1/4 (743) 7/8 (22)
B Blower Outlet Opening 4 (101) 33 (838) 51 x 31 (1295 x 787)
X
Y
0
CD
HUM
LV
HV
CWP
B
Note: Drawing Not To Scale.
Tolerance on all piping locating
dimensions ± 1/2" (13mm).
Front View
Section A-A
Front of Unit
DPN002035
Rev. 0
* Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm).
All units contain a factory-installed condensate trap. Do not trap external to the unit.
Drain line may contain boiling water. Select appropriate drain system materials.
The drain line must comply with all local codes.
** Optional Condensate Pump to be field-installed under unit.
35"
(889mm)
74" (1880mm)
31" (787mm)
Typical Air
Discharge Area
24-7/16" (620mm)
Typical Air
Discharge Area
24-1/8"
(613mm)
Air Discharge
Area
All Dimensions From
Right Rear Corner Of Unit
Including Panels
AA