Emerson Liebert Deluxe System/3 DE Installation Manual

Browse online or download Installation Manual for Unknown Emerson Liebert Deluxe System/3 DE. Emerson Liebert Deluxe System/3 DE Installation manual User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 64
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Precision Cooling
For Business-Critical Continuity
Liebert Deluxe System/3
- DX
Installation Manual - 50 and 60 Hz, 6-30 Ton DX Systems (DH/DE/VH/VE)
Page view 0
1 2 3 4 5 6 ... 63 64

Summary of Contents

Page 1 - Liebert Deluxe System/3

Precision CoolingFor Business-Critical ContinuityLiebert Deluxe System/3™ - DXInstallation Manual - 50 and 60 Hz, 6-30 Ton DX Systems (DH/DE/VH/VE)

Page 2 -

Introduction21.1.3 GLYCOOL™ (Chilled Glycol Cooling) SystemsGLYCOOL systems have all of the features of a compressorized water or glycol system, plus

Page 3 - TABLE OF CONTENTS

Installation32.0 INSTALLATION2.1 Room PreparationThe room should be well-insulated and must have a sealed vapor barrier. The vapor barrier in the ceil

Page 4

Installation42.3 Unit DimensionsFigure 1 Downflow (DH and DE models) cabinet and floor planning dimensional dataUNIT DIMENSIONAL DATAFLOOR CUTOUT DIME

Page 5

Installation5Table 1 Downflow (DH and DE models) dimensionsAir CooledWater CooledGlycol CooledGLYCOOLDimensional Datainches (mm) 60 Hz50 HzABCDEFGHJKL

Page 6

Installation6Figure 2 Upflow 6, 8 and 10 ton (VH and VE models) cabinet and floor planning dimensional data74" overall (1880mm)70" (1778mm)P

Page 7 - PRODUCT MODEL INFORMATION

Installation7Figure 3 Upflow 6, 8 and 10 ton (VH and VE models) blower duct and deck dimensional dataTable 2 Upflow 6, 8 and 10 ton (VH and VE models)

Page 8 - Table ii Unit weights

Installation8Figure 4 Upflow 15, 20 and 22 ton (VH and VE models) cabinet and floor planning dimensional dataAir return opening5-1/2"(140mm)33&qu

Page 9 - 1.0 INTRODUCTION

Installation9Figure 5 Upflow 15, 20 and 22 ton (VH and VE models) blower duct and deck dimensional dataTable 3 Upflow 15, 20 and 22 ton (VH and VE mod

Page 10 - Introduction

Installation10Figure 6 Upflow 30 ton (VH and VE models) cabinet and floor planning dimensional dataUNIT DIMENSIONAL DATA118"(2997mm)Plenum Flange

Page 11 - 2.0 INSTALLATION

Installation11Figure 7 Upflow 30 ton (VH and VE models) blower duct and deck dimensional dataTable 4 Upflow 15, 20 and 22 ton (VH and VE models) blowe

Page 13

Installation122.4 PipingAll fluid and refrigeration connections to the unit, with the exceptions of the condensate drain and live steam, are sweat cop

Page 14 - 20-1/4"

Installation13Figure 8 Electrical connection detailsRemote Heat Rejection ConnectionsDiagram is for directdrive air-cooledcondensers(for air-cooled un

Page 15

Installation14Figure 9 Electrical field connections NOTERefer to specification sheet for full load amp and wire size amp ratings.Monitoring panelField

Page 16 - 5/8" (16mm)

Installation152.6 Air Distribution Considerations2.6.1 Raised-Floor Air Flow Distribution ConsiderationsTo ensure proper air distribution, any unusual

Page 17 - (1930.4mm)

Installation162.6.3 Ducted Application InstallationDuct flanges are supplied on the blower outlets. Follow the SWACNA-Duct Construction Standard for s

Page 18

Installation17Figure 11 Plenum dimensional data for 6 - 22 ton modelsTable 6 Plenum dimensional data for 6 - 22 ton models, in. (mm)Model A B C D E FG

Page 19

Installation18Figure 12 Plenum dimensional data for 30 ton modelsTable 7 Plenum dimensional data for 30 ton models in. (mm)Model ABCDEFGHJKLGrilleFree

Page 20 - 2.5 Electrical Connections

Air Cooled Models193.0 AIR COOLED MODELS3.1 Condenser Location3.1.1 Outdoor Prop Fan ModelsThe air cooled condenser should be located for maximum secu

Page 21 - ROOM UNIT CONNECTIONS

Air Cooled Models203.3 Refrigerant PipingAll refrigeration piping should be installed with high temperature brazed joints. Prevailing good refrigerati

Page 22

Air Cooled Models21Figure 13 Piping: Fan speed control condensers Table 9 Fan speed control condenser piping connection sizes - Cu ODCondenser ModelNu

Page 23

iTABLE OF CONTENTSPRODUCT MODEL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .V1.0 I

Page 24 - 2.6.5 Filter Box Installation

Air Cooled Models22Figure 14 Piping: Lee-Temp control condensersTable 10 Lee-Temp control condenser piping connection sizesCondenser Connections-ODSin

Page 25 - DPN000620 Rev0

Air Cooled Models23Figure 15 Downflow air cooled (DH) piping connectionsTable 11 Downflow air cooled (DH) piping connection sizes, inchesAir Cooled Mo

Page 26 - DPN000621 Rev0

Air Cooled Models24Figure 16 Upflow air cooled (VH) piping connectionsTable 12 Factory provided piping connection sizes, inches, upflow air cooled (VH

Page 27 - 3.0 AIR COOLED MODELS

Air Cooled Models25Figure 17 Outdoor air cooled 1-4 fan condenser cabinet and anchor dimensional dataEyebolts for liftingcondenser provided on four-fa

Page 28 - 3.3 Refrigerant Piping

Air Cooled Models26Table 13 Outdoor air cooled 1-4 fan condenser physical dataModelCSF/CDF1# ofFansABCDTotal HeatRejection 60 Hz3CFM(l/s)60 Hz2Total H

Page 29

Air Cooled Models27Figure 18 Outdoor air cooled 6 and 8 fan condenser cabinet and anchor dimensional dataTable 14 Outdoor air cooled 6 and 8 fan conde

Page 30

Air Cooled Models28Figure 19 Air cooled model general arrangement diagramNOTETwo refrigeration circuits required - Single circuit shown only for clari

Page 31 - DPN000536_Rev0

Air Cooled Models29Figure 20 Piggyback condenser cabinet and floor planning dimensional data NOTEA 1” (25.4mm) flange is provided on all units for duc

Page 32 - DPN000537 Rev0

Air Cooled Models30Figure 21 Piggyback condenser piping connectionsTable 17 Piggyback condenser piping connection dimensional dataModelDimensional Dat

Page 33

Air Cooled Models313.4 Fan Speed Control SystemsFan Speed Control provides an infinite number of speed variations on specially designed permanent spli

Page 34

ii4.1 Drycooler Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 364.1.1

Page 35 - 37-7/8"

Air Cooled Models32Table 19 Indoor unit approximate refrigerant charge lb (kg.) R–22Model 60 Hz (50 Hz)Refrigerant Charge/Circuit75A 4.0 (1.8)114A (11

Page 36

Air Cooled Models333.5 Lee-Temp/Flood Back Head Pressure Control SystemsThe Lee-Temp system consists of a modulating type head pressure control valve

Page 37 - FAN DISCHARGE DATA

Air Cooled Models343.5.4 Charging1. Make sure unit is OFF and that jumper is removed on Fan Safety Switch.2. Connect a set of manifold gauges to the r

Page 38

Air Cooled Models35Figure 23 Lee-Temp control typical general arrangement diagramCondenser CoilTraps* every25’ (7.6m) of rise on hot gas line onlySole

Page 39 - 3.4 Fan Speed Control Systems

Glycol Cooled/GLYCOOL™ Models364.0 GLYCOL COOLED/GLYCOOL™ MODELS4.1 Drycooler Location4.1.1 Outdoor Prop Fan ModelsThe drycooler should be located for

Page 40

Glycol Cooled/GLYCOOL™ Models37Table 23 Room dew point temperatures °F (°C)Dry Bulb Wet Bulb Relative Humidity Dew Point70 (21.1) 57.2 (14.0) 45 48.9

Page 41 - 3.5.3 Dehydration

Glycol Cooled/GLYCOOL™ Models38Figure 24 Downflow glycol cooled (DH) piping connectionsTable 28 Downflow glycol cooled (DH) piping connection sizes, i

Page 42 - 3.5.5 Refrigerant Level

Glycol Cooled/GLYCOOL™ Models39Figure 25 Upflow glycol cooled (VH) piping connectionsTable 29 Factory-provided piping connection sizes, inches, upflow

Page 43

Glycol Cooled/GLYCOOL™ Models40Figure 26 Downflow GLYCOOL™ cooled (DE) piping connectionsTable 30 Downflow GLYCOOL (DE) piping connection sizes, inche

Page 44 - 4.4 Glycol Piping

Glycol Cooled/GLYCOOL™ Models41Figure 27 Upflow GLYCOOL™ cooled (VE) piping connectionsTable 31 Upflow GLYCOOL (VE) piping connection sizes, inchesGLY

Page 45

iiiFIGURESFigure 1 Downflow (DH and DE models) cabinet and floor planning dimensional data . . . . . . . . . . . . . . . . 4Figure 2 Upflow 6, 8 and

Page 46 - DPN000572_Rev0

Glycol Cooled/GLYCOOL™ Models42Figure 28 1-4 fan drycooler cabinet and anchor dimensional dataTable 32 Glycol pump dataPump Pump SuctionConnectionin.P

Page 47

Glycol Cooled/GLYCOOL™ Models43Table 33 1-4 fan drycooler physical dataModel(Notes2,3,4)# ofFansABCDCFM(l/s)60 Hz1CFM(l/s)50 Hz1InternalVolumegal. (l)

Page 48 - DPN000588_Rev0

Glycol Cooled/GLYCOOL™ Models44Figure 29 6- and 8-fan drycooler cabinet and anchor dimensional dataTable 34 6- and 8-fan drycooler physical dataModel#

Page 49

Glycol Cooled/GLYCOOL™ Models454.5 Preparation of Glycol SolutionsTypical ethylene glycol manufacturers and suppliers are Union Carbide (Ucartherm) or

Page 50 - Table 32 Glycol pump data

Glycol Cooled/GLYCOOL™ Models46Figure 30 Glycol general arrangementFilter DryerSight GlassSolenoid ValvesExpansion ValveHot Gas Bypass (optional)Muffl

Page 51

Glycol Cooled/GLYCOOL™ Models47Figure 31 GLYCOOL™ general arrangement* Components are not supplied by Liebert but are recommended for proper circuit o

Page 52

Water Cooled Models485.0 WATER COOLED MODELS5.1 Piping ConsiderationsManual shut-off valves should be installed at the supply and return lines of each

Page 53 - Glycol Cooled/GLYCOOL™ Models

Water Cooled Models49Figure 32 Water cooled general arrangementEvaporator CoilExpansion ValveSolenoid ValvesSight GlassFilter DryerShutoff ValveHot Ga

Page 54

Water Cooled Models50Figure 33 Downflow water cooled (DH) piping connectionsTable 36 Downflow water cooled (DH) piping connection sizes, inchesWater C

Page 55 - general arrangement

Water Cooled Models51Figure 34 Upflow water cooled (VH) piping connectionsInstall fieldpipingthroughfactory-supplied cover plate(not shown for clarity

Page 56 - 5.0 WATER COOLED MODELS

ivTABLESTable i Model number designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 57 - Field Piping

Water Cooled Models52Table 37 Factory-provided piping connection sizes, inches, upflow water cooled (VH)Water Cooled ModelsAOD CuBOD CuCNPT FEMALEDOD

Page 58 - E - Steam Reheat Return Line

Water Cooled Models53NOTES

Page 59 - Optional Steam Reheat

Water Cooled Models54

Page 61 - Water Cooled Models

Ensuring The High Availability0f Mission-Critical Data And Applications.Emerson Network Power, the global leader in enabling business-criticalcontinui

Page 62

vPRODUCT MODEL INFORMATIONEquipment InspectionUpon arrival of the unit, inspect all items for either visible or concealed damage. Damage should be imm

Page 63

viTable ii Unit weightsCapacity and Cooling Type Weight lbs (kg)Air Cooled ModelsDH/VH, 60 (50) Hz75A 1205 (547)114A (115A) 1425 (647)125A (130A) 1440

Page 64

Introduction11.0 INTRODUCTION1.1 System DescriptionsDeluxe System/3 environmental control systems are available in several configurations. Each config