Air Cooled Models
23
Figure 15 Downflow air cooled (DH) piping connections
Table 11 Downflow air cooled (DH) piping connection sizes, inches
Air Cooled Models
60 Hz (50 Hz)
A
(AO Cu)
B
(OD Cu)
C
(NPT Male)
D
(OD Cu)
E
(NPT Male)
F
(OD Cu)
DH075A (DH075A) 5/8 1/2 1/2 5/8 1/2 5/8
DH114A (DH115A) 5/8 1/2 1/2 5/8 1/2 5/8
DH125A (DH130A) 5/8 1/2 1/2 5/8 1/2 5/8
DH199A (DH199A) 7/8 1/2 3/4 7/8 3/4 7/8
DH245A (DH245A) 1-1/8 5/8 3/4 7/8 3/4 7/8
DH290A (DH290A) 1-1/8 5/8 NA NA NA NA
DH380A (DH380A) 1-1/8 5/8 NA NA NA NA
MONITORING
PANEL
NOTE: Install all piping
per local codes.
Condensate Drain. Field pitch a min. of
1/8" (3.2mm) per ft. (305mm). 3/4" NPT for units
without factory installed condensate pump. Do
not install an external trap. 1/2" OD CU for units
with factory installed condensate pump.
1/4" OD CU Humidifier Supply Line (Steam Gen./Infrared)
B - Liquid Refrigerant Lines.
A
- Hot Gas Refrigerant Lines (Field install factory
supplied muffler on 245A, 290A and 380A models).
C
- Steam Reheat Supply Line
D - Hot Water Reheat Supply Line.
E - Steam Reheat Return Line (Field
install factory supplied steam
trap with vacuum breaker).
F - Hot Water Reheat Return Line.
1/2"
NPT Male Steam
Humidifier Supply Line.
1/2" NPT Male Steam
Humidifier Return Line
DPN000536_Rev0