Emerson Liebert Deluxe System/3 DE Installation Manual Page 45

  • Download
  • Add to my manuals
  • Print
  • Page
    / 64
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 44
Glycol Cooled/GLYCOOL™ Models
37
Table 23 Room dew point temperatures °F (°C)
Dry Bulb Wet Bulb Relative Humidity Dew Point
70 (21.1) 57.2 (14.0) 45 48.9 (8.9)
70 (21.1) 58.5 (14.7) 50 50.5 (10.3)
72 (22.2) 58.9 (14.9) 45 50.0 (10.0)
72 (22.2) 60.0 (15.5) 50 52.4 (11.3)
75 (23.8) 61.2 (16.2) 45 52.4 (11.3)
75 (23.8) 62.5 (16.9) 50 55.0 (12.7)
*Minimum glycol temperature before condensation will occur.
Table 24 Glycol concentration
% Glycol by
Volume 0102030 40 50
Freezing Point
°F (°C) 32 (0) 25 (-3.9) 16 (-8.9) 5 (-15.0) -10 (-23.3) -32 (-35.5)
Apparent specific
Gravity @ 50
°F (10°C)
1.000 1.014 1.028 1.042 1.057 1.071
Table 25 Refrigerant control settings for glycol cooled units—psi (kPa)
Refrigerant Type Low Pressure Cut Out Low Pressure Cut In High Pressure Cut Out
R–22 20 (137.9) 65 (448.2) 360 (2482)
Table 26 Deluxe glycol volume approximate gal. (l) max
Model
(50 Hz)
Glycol
Cooled
GLYCOOL
Upflow Downflow
—72G 2.0 (7.5) 9.0 (34.0) 8.5 (32.0)
—110G/(111G) 2.0 (7.5) 9.0 (34.0) 8.5 (32.0)
—116G/(121G) 2.5 (9.5) 10.0 (38.0) 10.0 (38.0)
—192G 4.5 (17.0) 14.0 (53.0) 13.5 (51.0)
—240G 5.5 (21.0) 15.0 (57.0) 15.0 (57.0)
—265G 5.5 (21.0)
—363G 6.5 (24.6) 18.0 (68.1) 18.0 (68.1)
Table 27 Volume in standard Type L copper piping
Diameter (in.) Volume
Outside Inside gal./ft. l/m
1/2 0.123 0.008 0.01
5/8 0.545 0.012 0.15
3/4 0.666 0.018 0.22
7/8 0.785 0.025 0.31
1-1/8 1.025 0.043 0.53
1-3/8 1.265 0.065 0.81
1-5/8 1.505 0.092 1.15
2-1/8 1.985 0.161 2.00
2-5/8 2.465 0.248 3.08
3-1/8 2.945 0.354 4.40
3-5/8 3.425 0.479 5.95
4-1/8 3.905 0.622 7.73
Page view 44
1 2 ... 40 41 42 43 44 45 46 47 48 49 50 ... 63 64

Comments to this Manuals

No comments