Installation
11
Figure 8 Rotate the operation and display panel
c. Pull the logo on the front plastic bezel cover, rotate it 90 degrees clockwise and snap it back
into position. The rotated front plastic bezel cover is shown in Figure 9.
d. Replace the front plastic bezel cover on the Liebert GXT3. At this point, the UPS operation
and display panel and logo have been rotated 90 degrees clockwise, which provides upright
viewing for users.
5. Place the Liebert GXT3 and any battery cabinets on the support bases. Each Liebert GXT3 needs
four support bases, as shown in Figure 9.
Figure 9 Tower installation
2.4.2 Rack Installation
To install a Liebert GXT3 UPS in a rack:
1. Unpack the two bracket assemblies and mounting hardware from the rack-mounting kit
(P/N: RMKIT18-32). Bracket assembly includes inner member, front member and rear member.
NOTE
When the Liebert GXT3 is installed in a rack, the UPS must be supported by a shelf,
brackets, or slide rails on each side. The factory-supplied rack-mount ears cannot support
the weight of the UPS. They are used to move the UPS into and out of the rack and attach the
UPS to the rack.
Mounting hardware and slide rails are sold separately. Contact your local dealer or
Emerson representative for these options and any assistance.
Operation and Display Panel
Rotated Clockwise 90 Degrees
Operation and
Display Panel
Rotated for
Tower Operation
Support Bases
Support Bases
Liebert GXT3 UPS
Liebert GXT3 UPS and
External Battery Cabinet
Page view 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 43 44

Comments to this Manuals

No comments