Emerson XEV22D Service Manual Page 2

  • Download
  • Add to my manuals
  • Print
  • Page
    / 6
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 1
1592025990 XEV22D GB r1.5 14.11.2014.docx XEV22D 2/6
PP07 PP11, PP30, 4÷20mA pressure
transducers:
Set parameter tPP = 420.
Connect:
Brown wire (+) to terminal 19;
White wire (-) to terminal 20
PP
R15 PPR30
Ratiometric transducers
(0.5÷4.5Vdc)
Set parameter tPP = 5U
Connect:
Brown wire (+) to terminal 18;
White wire (in) to terminal 20;
Green wire (gnd) to terminal 21
Temperature probe:
Set parameter
ttE = NTC: (NTC 10K) or
ttE = Pt1: (Pt1000) or
ttE = CtC: (NTC-US 10K)
Connect to terminals 13-14
4.6 CONFIGURABLE DIGITAL INPUT CONNECTION
The superheat regulation is performed only when the cooling digital input is enabled.
It’s possible to enable the SH regulation via:
- Digital input 1, free voltage contact:
Use the terminals (14-15), set the parameter i1F = CCL, its polarity it’s set by par. i1P.
- Digital input 2 (8-9), main voltage contact
Use the terminals (8-9), set the parameter i2F = CCL, its polarity it’s set by par. i1P
Usually the digital input is connected to a thermostat or an activation contact
T= Thermostat ( or activation contact)
V= Stepper valve (mono or bipolar)
P1= Temperature sensor (PT1000 o
NTC or NTC-US)
P2= Pressure transducer 4..20mA or
ratiometric (0-5Vdc).
4.7 SUPPLY CONNECTION
Power supply: XEV22D is powered at 24Vac/dc.
Use Class 2 transformer at list 20VA as the TF20D
Connect transformer to terminals 11-12.
4.8 VALVE CONFIGURATION
4.8.1 BEFORE CONNETTING THE VALVE
- ALWAYS CONNECT OR DISCONNET THE VALVE WHEN THE CONTROLLER IS NOT
POWERED
- CONFIGURE THE VALVE ON THE XEV22D BEFORE CONNECTING THE VALVE
1. BEFORE CONNECTING the valve, to avoid possible problems, configure the driver by making
the right changes on the parameters.
2. The max distance between an XM controller and a valve must not exceed 10 m. To avoid any
problems, use only shielded cables with section greater than or equal to 0.325 mm² (AWG22).
3. Select the kind of motor (tEU parameter) and check if the valve is present in tEP parameter
table reported here below.
tEP LSt
(steps*10)
uSt
(steps*10)
CPP
(mA*10)
CHd
(mA*10)
Sr
(step/s)
tEu
(bip/unip)
HSF
(Half/full)
1
Danfoss
ETS-25/50
7 262 10 10 300 bP FUL
2
Danfoss
ETS-100
10 353 10 10 300 bP FUL
3
Danfoss
ETS-
250/400
11 381 10 10 300 bP FUL
4
Sporlan
SEI 0.5-11
0 159 16 5 200 bP FUL
5
Sporlan
SER 1.5-20
0 159 12 5 200 bP FUL
6
Sporlan
SEI 30
0 319 16 5 200 bP FUL
7
Sporlan
SER(I)
G,J,K
0 250 12 5 200 bP FUL
8
Sporlan
SEI 50
0 638 16 5 200 bP FUL
9
Sporlan
SEH(I) 100
0 638 16 5 200 bP FUL
10
Sporlan
SEH(I) 175
0 638 16 5 200 bP FUL
11
Emerson
EX4-EX5-
EX6
5 75 50 10 500 bP FUL
12
Emerson
EX7
10 160 75 25 500 bP FUL
13
Emerson
EX8 500
10 260 80 50 500 bP FUL
14
Emerson
EX3
4 33 0 0 50
uP HAF
Liability Limitation
All the pre-sets have been done according to the documentation available when the XEV22D has been
released, see below reference:
Danfoss:
- DKRCC.PD.VD1.C6.02 / 520H8021 @ Danfoss A/S (AC-MCI / sw), 2014-07
Sporlan:
- 92008 / Bulletin 100-20
- RACE Catalogue 100-20-3 EDEV-2/UK - 02/2013
Emerson
- FC-TD/ EX4-8 July 2008
In any case for each valve the only reference is given by the manual released by the manufacture
together with the valve.
Dixell can’t be considered responsible for any change made by the manufacturer and reported on the
manufacturer manual.
4.8.2 Manual setting of valve
To set the valve manually, act the according to the following procedure:
a. Set tEP=0
b. Then set following parameters: LSt, USt, Sr, CPP, CHd according to the valve manual
4.9 VALVE CONNECTION
4.9.1 TERMINALS FOR VALVE CONNECTION
4 WIRES VALVES (BIPOLAR)
Connection
numbering
ALCO EX
SPORLAN
SEI-SEH
DANFOSS
ETS
4 BLUE WHITE BLACK
2 BROWN BLACK WHITE
3 BLACK RED RED
1 WHITE GREEN GREEN
5-6 WIRES VALVES (UNIPOLAR)
Connection
numbering
EMERSON
EX3
SPORLAN SAGINOMIYA
4
BLUE
ORANGE ORANGE
2
BLACK
RED RED
3
BROWN
YELLOW YELLOW
1
WHITE
BLACK BLACK
5 – Common
GRAY
GRAY GRAY
AFTER MAKING THE CONNECTION, PLEASE SWITCH OFF AND ON THE XEV CONTROLLER IN
ORDER TO BE SURE OF THE RIGHT POSITIONING OF THE VALVE.
4.10 ABSOLUTE MAXIMUM POWER
XEV22D is able to drive a wide range of stepper valves, in the following table are indicated the
maximum values of current that the actuator can supply to the stepper wiring. The Dixell transformer to
use is the TF20D.
NOTE: the electrical power absorption of the valve can be unrelated to refrigeration power that valve
has. Before using the actuator, please read the technical manual of the valve supplied by the
manufacturer and check the maximum current used to drive the valve in order to verify that they are
lower than those indicated below.
VALVE
TYPE
BIPOLAR VALVES
(4 wires)
Maximum Current 0.9A
UNIPOLAR VALVES
(5-6 wires)
Maximum Current 0.33A