Emerson XEV22D Service Manual Page 4

  • Download
  • Add to my manuals
  • Print
  • Page
    / 6
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 3
1592025990 XEV22D GB r1.5 14.11.2014.docx XEV22D 4/6
tEP Predefined valve selection: (0 to 14)
MODEL LSt
(steps*10)
uSt
(steps*10)
CPP
(mA*10)
CHd
(mA*10)
Sr
(step/s)
tEu
(bip/unip)
HSF
(
Half/full)
1
Danfoss
ETS-25/50
7 262 10 10 300 bP FUL
2
Danfoss
ETS-100
10 353 10 10 300 bP FUL
3
Danfoss
ETS-
250/400
11 381 10 10 300 bP FUL
4
Sporlan
SEI 0.5-11
0 159 16 5 200 bP FUL
5
Sporlan
SER 1.5-20
0 159 12 5 200 bP FUL
6
Sporlan
SEI 30
0 319 16 5 200 bP FUL
7
Sporlan
SER(I)
G,J,K
0 250 12 5 200 bP FUL
8
Sporlan
SEI 50
0 638 16 5 200 bP FUL
9
Sporlan
SEH(I) 100
0 638 16 5 200 bP FUL
10
Sporlan
SEH(I) 175
0 638 16 5 200 bP FUL
11
Emerson
EX4-EX5-
EX6
5 75 50 10 500 bP FUL
12
Emerson
EX7
10 160 75 25 500 bP FUL
13
Emerson
EX8 500
10 260 80 50 500 bP FUL
14
Emerson
EX3
4 33 0 0 50
uP HAF
Liability Limitation
All the pre-sets have been done according to the documentation available when the
XEV22D has been released, see below reference:
Danfoss:
- DKRCC.PD.VD1.C6.02 / 520H8021 @ Danfoss A/S (AC-MCI / sw), 2014-
07
Sporlan:
- 92008 / Bulletin 100-20
- RACE Catalogue 100-20-3 EDEV-2/UK - 02/2013
Emerson
- FC-TD/ EX4-8 July 2008
In any case for each valve the only reference is given by the manual released by the
manufacture together with the valve.
Dixell can’t be considered responsible for any change made by the manufacturer and
reported on the manufacturer manual.
Manual valve setting
To set the valve manually, act the according to the following procedure:
a. Set tEP=0
b. Then set following parameters: LSt, USt, Sr, CPP, CHd according to the valve
manual
HFS Kind of motor movement: (HAF; FUL)
HAF = half step. Use this setting for the unipolar valve.
FUL = full step. Use this setting for the bipolar valve.
LSt Minimum number of steps: (0 to USt (*10)) it permits to select the minimum number
of steps. At this number of steps the valve should be closed. So it’s necessary the
reading of manufacturer datasheet to set correctly this parameter. It’s the minimum
number of steps to stay in advised range of functioning.
!!!!! WARNING !!!!! after changing this parameter the valve will have to be
reinitialized. The device performs this procedure automatically and restarts its
normal functioning when the programming mode ends.
USt Maximum number of steps: (LSt to 800 (*10)) it permits to select the maximum
number of steps. At this number of steps the valve should be completely opened. Read
the datasheet provided by manufacturer of the valve to set correctly this parameter. It’s
the maximum number of steps to stay in advised range of functioning. !!!!! WARNING
!!!!! after changing this parameter the valve will have to be reinitialized. The
device performs this procedure automatically and restarts its normal functioning
when the programming mode ends.
ESt Extra step in closing phase: (0 to 255 (*10)) it sets the number of extra steps the
controller performs, when the valve is closed at start up, to force the closure of the
valve.
Sr Step rate: (10 to 600 step/sec) it is the maximum speed to change step without losing
precision (=losing steps). It’s advised to stay under the maximum speed.
CPP Current per phase (only bipolar valves): (0 to 100 (*10mA)) it is the maximum current
per phase used to drive valve. It’s used only with bipolar valves.
CHd Holding current per phase (only bipolar valves): (0 to 100 (*10mA)) it is the current
per phase when the valve is stopped for more than 4 minutes. It’s used only with
bipolar valves.
oPE Start opening Percentage: (0 to 100%) opening valve percentage when start function
is active and during post defrost phase. This phase duration is SFd time.
SFd Start Function duration: (0.0 to 42min 00s, res. 10s) it sets start function duration and
post-defrost duration. During this phase the alarms are not enabled.
dty Pilot duty: (2-10dec/sec) To reach the final position the valve moves for Ton sec and
stops for Tof sec, where Ton and Tof are defined as in the following:.
Ton= dty/10s
Toff= (1-dty/10)s
Note: with dty=10 the Pilot duty function is disabled.
With bipolar valve, during the Toff time the maintenance current is used.
MnF Maximum opening percentage at normal Functioning: (0 to 100%) during regulation
it sets the maximum valve opening percentage.
FoP Forced Opening percentage: (0 to 100; nU) if FoP=nU valve works with regulation
algorithm. If FoP is different from nU the valve stays at FoP opening percentage. This
function could be useful during plant starting or during service operations.
PI PARAMETERS (trained staff)
AMS
Self self adaptive SH regulation enabling: parameter enables the self adaptive
regulation of the superheat
no = standard regulation using the PID parameters (Pb, rS, inC, dFC)
yES = self-adaptive regulation, controller regulates SH automatically, setting the PID
parameter
Atu
Minimum STABLE superheat search (No; yES) This parameter enables the search of
the minimum stable superheat. The lowest admitted value is LSH+2°C
Pb
Proportional band:
(0.1 to 50.0°C; 1 to 90°F)
PI proportional band. A value
bigger than 5°C is advised.
rS
Band Offset:
(-12.0 to 12.0°C; -21 to 21°F)
PI band offset. It permits to
move the proportional band of
the PI. With rS=0 the band is
between [SEt to SEt+Pb].
inC Integration time: (0 to 255s) PI integration time.
dFc Derivative time (0 to 255s) PID derivative time.
PROBE PARAMETERS
tPP Type of Pressure transducer: (420; 5V; LAn) it sets type of pressure transducer to
use. 420 = 4 to 20mA pressure transducer; 5V = 0 to 5V ratiometric transducer; LAn =
the pressure signal comes from another XEV module.
LPP Enable pressure probe sending in LAN: (n; Y) if LPP=Y the value of pressure read
by device is sent in LAN. Only one device of the LAN can have LPP=Y.
PA4 Probe value at 4mA or at 0V: (-1.0 to P20 bar; -14 to P20 psi) pressure value
measured by probe at 4mA or at 0V (related to PrM parameter).
P20 Probe value at 20mA or at 5V: (PA4 to 50.0 bar; PA4 to 725 psi) pressure value
measured by probe at 20mA or at 5V (related to PrM parameter).
oPr Pressure probe calibration: -12.0 to 12.0 bar; -174 to 174 psi.
ttE Type of temperature probe: (PtM; ntC) it allows to set the kind of probe used by the
instrument: PtM = PT1000 probe, ntC = NTC-US probe.
otE Temperature probe calibration: -12.0 to 12.0°C; -21 to 21°F.
DIGITAL INPUTS
i1P Digital Input 1 (Free of voltage) digital input polarity: (cL, oP) CL = activated when
closed; oP = activated when opened.
i1F Digital Input 1 (Free of voltage) digital input function: (CCL, rL) CCL = cooling call;
rL = digital input activates relay.
d1d Digital Input 1 (Free of voltage) activation delay: (0 to 255 min) this activation delay
is used only if digital input is configured as rL.
i2P Digital Input 2 (High voltage) digital input polarity: (CL, oP) CL = activated when
closed; oP = activated when opened.
i2F Digital Input 2 (High voltage) digital input function: (CCL, rL) CCL = cooling call;
rL = digital input activates relay.
d2d Digital Input 2 (High voltage) activation delay: (0 to 255 min) this activation delay is
used only if digital input is configured as rL.
ALARM
dAo Alarm delay after restarting regulation: (0.0 to 42min 00s, res. 10s) time between
digital input activation (configured as CCL) and alarm signalling. The LSH alarm is
always signalled also during this time.
tdA Type of alarm signalled by relay: (ALL, SH, PrE, di) ALL = all alarm; SH = superheat
alarm; PrE = pressure alarm; di = activation only when digital input configured as rL is
active.
LPL Lower Pressure Limit for superheat regulation: (PA4 to P20 bar; PA4 to P20 psi)
when suction pressure comes down to LPL, the regulation is performed with a LPL
fixed value for pressure. When suction pressure comes back to LPL, the normal
pressure value is used (related to PrM parameter).
MoP Maximum Operating Pressure threshold: (LoP to P20bar; LoP to P20 psi) if suction
pressure exceeds maximum operating pressure value, the instrument signals this
situation with an alarm LED (related to PrM parameter).
LoP Lowest Operating Pressure: (PA4 to MoP bar; PA4 to MoP psi) if the suction pressure
comes down to this value, a low pressure alarm will be signalled with an alarm LED
(related to PrM parameter).
PHY Pressure alarm Hysteresis: (0.1 to 5.0 bar, 1 to 72 psi) pressure hysteresis to disable
alarm signalling.
dML Delta MoP-LoP: (0 to 100%) when a MoP alarm occurs valve will close of the dML
percentage every one second until MoP alarm is active. When LoP occurs, valve will
open of the dML percentage every one second until LoP alarm is active.
MSH Maximum SuperHeat alarm: (LSH to 80.0°C; LSH to 144°F) when superheat exceeds
this value, an high superheat alarm will be signalled after interval SHd.
Page view 3
1 2 3 4 5 6

Comments to this Manuals

No comments