should be used for repairing Fisher
®
regulators. Restart gas utilization equipment
according to normal startup procedures.
General Maintenance
1. Visually inspect the regulator and its parts for
any damage.
2. Ensure tight connections, tight seals and safe operation.
If there is evidence of leakage or unstable internal
motion, a rebuild with seal replacement and relubrication
may be necessary.
3. Observe the blanketing pressure.
4. Inspect the inlet pressure for the proper pressure
(stamped on the regulator nameplate).
Body Area
Perform the following procedure to gain access to the
disk assembly, orice, body O-ring and pitot tube if used.
Release all pressure from the diaphragm casing and open
the disk assembly before performing the following steps.
Key numbers are referenced in Figures 7 and 8.
1. Remove the cap screws (key 2) and separate the
diaphragm casing (key 4) from the body (key 1).
2. Remove and inspect the body seal O-ring (key 11) and
the backup ring (key 49). See Figure 5.
3. Inspect and replace the orice (key 5) if necessary.
Protect the orice seating surface during disassembly
and assembly. Lubricate the threads of the replacement
orice with a good grade of light grease and install with
340 to 470 inch- pounds / 38.5 to 53.1 N•m of torque.
4. Remove the cotter pin (key 15) to replace the disk
assembly (key 13). If not necessary, skip to step 8.
5. To replace the pitot tube (key 32, Figure 7) on the
Type T205, remove the pitot tube machine screws
(key 17), install the new pitot tube and secure with the
pitot tube machine screws (key 17) using 14 to
19 inch-pounds / 1.6 to 2.1 N•m of torque. Position the
pitot tube so that it points into the outlet of the body by
rotating the guide insert (key 18).
6. To inspect the throat seal O-ring (key 31, Figure 8) on
the Type T205M, remove the machine screw (key 34,
Figure 8). Replace if necessary and reassemble.
7. Install the disk assembly (key 13) and secure it with the
cotter pin (key 15). Bend the cotter pin end using pliers
or equivalent tool (see Figure 6).
8. Place back-up ring (key 49) into the body (key 1). Then
place the body seal O-ring (key 11) into the body. See
Figure 5.
9. Place the diaphragm casing (key 4) on the body (key 1).
Secure the diaphragm casing to the body with the cap
screws (key 2) using 90 to 126 inch-pounds / 10.2 to
14.2 N•m of torque.
Diaphragm and Spring Case Area
Perform the following procedure to gain access to the
spring, diaphragm, lever assembly and stem. Release all
pressure from the diaphragm casing before performing the
following steps.
Note
Remove any remote control drive unit used
with a T205 Series regulator from the spring
case (key 3) before performing these steps.
1. For internal at circular adjusting screw – remove
the closing cap (key 22) and closing cap gasket
(key 25).
For external square head adjusting screw – loosen
the locknut (key 20).
2. Turn the adjusting screw (key 35) counterclockwise
to remove all the compression from the control spring
(key 6).
3. If the only maintenance procedure to be performed is
the changing of the control spring (key 6):
BODY MATERIAL END CONNECTION STYLE
(1)
PART NUMBER
3/4-inch / DN 20 Body 1-inch / DN 25 Body
Gray Cast iron NPT ERSA01588A0 ERSA01755A0
WCC Carbon steel
NPT ERSA00230A1 ERSA00194A1
CL150 RF ERSA01469A0 ERSA01469A1
CL300 RF ERSA01469A2 ERSA01469A3
PN 16/25/40 RF ERSA01469A4 ERSA01469A5
Stainless steel
NPT
(2)
ERSA00230A0 ERSA00194A0
CL150 RF ERSA01469A6 ERSA01469A7
CL300 RF ERSA01469A8 ERSA01469A9
PN 16/25/40 RF ERSA01469B0 ERSA01469B1
1. All anges are welded. Weld-on ange dimension is 14 inches / 356 mm face-to-face.
2. NACE Standard MR0175-2002.
Table 4. Body Materials and Part Numbers (Body, key 1)