T205 Series
6
2. Slowly open the supply line shutoff valve (to the
blanketing valve) and leave it fully open.
3. Monitor the tank vapor space pressure.
Adjustment
WARNING
!
To avoid personal injury, property damage
or equipment damage caused by bursting
of pressure containing parts or explosion of
accumulated gas, never adjust the control
spring to produce an outlet pressure higher
than the upper limit of the outlet pressure
range (see Table 2) for that particular spring.
If the desired outlet pressure is not within
the range of the control spring, install a
spring of the proper range according to the
Diaphragm and Spring Case Area section of
the maintenance procedure.
Adjust the regulator control pressure setting to meet the
requirements of the speci c application. With a spring-
loaded regulator, the pressure setting may be adjusted to a
value within the spring range shown in Table 3. To adjust the
pressure setting, perform the following steps (key numbers
are referenced in Figures 6 and 7):
For internal  at circular adjusting screw:
1. Remove the closing cap (key 22).
2. Use a 1-inch / 25 mm hex rod or  at screwdriver to turn
the adjusting screw (key 35) either clockwise to increase
outlet pressure or counterclockwise to decrease outlet
pressure. The regulator will go into immediate operation.
To ensure correct operation, always use a pressure
gauge to monitor the tank blanketing pressure when
making adjustments.
3. After making the adjustment, replace the closing cap
gasket (key 25) and install the closing cap (key 22).
For external square head adjusting screw:
1. Loosen the locknut (key 20).
2. Turn the adjusting screw (key 35) either clockwise
to increase outlet pressure or counterclockwise to
decrease outlet pressure. Always use pressure gauge
to monitor the tank blanketing gas pressure when
making adjustments.
3. After making the adjustment, tighten the locknut
(key 20).
Shutdown
1. Close the nearest upstream shutoff valve.
2. Close the nearest downstream shutoff valve to vent the
regulator properly.
3. For a regulator with control line: Close the valve in
the control line and vent the diaphragm casing to
the atmosphere.
4. Open the vent valve between the regulator and the
downstream shutoff valve nearest to it. All pressure
between these shutoff valves is released through the
open vent valve, since a T205 Series remains open in
response to the decreasing downstream pressure.
Maintenance
Regulator parts are subject to normal wear and must be
inspected and replaced as necessary. The frequency
of inspection and replacement of parts depends upon
the severity of service conditions or the requirements
of local, state and federal regulations. Due to the care
Regulator Technologies takes in meeting all manufacturing
requirements (heat treating, dimensional tolerances, etc.),
use only replacement parts manufactured or furnished by
Regulator Technologies.
WARNING
!
To avoid personal injury, property damage or
equipment damage caused by sudden release
of pressure or explosion of accumulated
gas, do not attempt any maintenance or
disassembly without  rst isolating the
regulator from system pressure and relieving
all internal pressure from the regulator.
Regulators that have been disassembled for
repair must be tested for proper operation
before being returned to service. Only parts
Figure 5. Expanded View of the Body Area Showing the Body
Seal O-ring and Backup Ring Placement
Figure 6. Proper Bending of Cotter Pin (key 15)
COTTER PIN (KEY 15)
BODY SEAL
O-RING (KEY 11)
BODY (KEY 1)
BACKUP RING
(KEY 49)