Emerson FTA1100-H Datasheet Page 2

  • Download
  • Add to my manuals
  • Print
  • Page
    / 4
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 1
Class 1, Division 2 hazardous locations, T3
temperature rating.
time and date stamp. The display is a 128x64 Backlit
LCD capable of customized graphics. The display
and interface are NEMA rated for Type 2, 3R, 4, 4X,
and 12 protection and is fully accessible without
opening the controller door. The user interface
utilizes multiple levels of password protection for
system security. A minimum of 3 password levels
are provided.
Enclosures
The standard enclosures are NEMA Type 4X (IEC
IP66), 12 Gauge, Seam Welded, #316 Stainless
Steel, Polished and Brushed nish. The controller
should be installed in an area with protection from
direct sunlight and with an ambient temperature
above 41
º F (5º C). Optional enclosure types include:
– NEMA Type 4X (IEC IP66), 12 Gauge, Seam
Welded, #316 Stainless Steel, Painted Finish
NEMA enclosures listed meet or exceed referenced
IEC designations.
Approvals
Firetrol fire pump controllers are listed by Un-
derwriters’ Laboratories, Inc., in accordance with
UL1604, Electrical Equipment for Use in Class 1 and
II, Division 2, and Class III Hazardous (Classi ed) Loca-
tions and UL698, Industrial Control Equipment for Use
Firetrol
®
FTA1100H combined automatic and
manual Mark II based diesel engine re pump con-
trollers are intended for starting and monitoring re
pump diesel engines in Class1, Division 2 hazard-
ous locations. The controllers have a temperature
rating of T3. They are available for use with 12 or
24 volt negative ground systems using lead acid or
Nickel-Cadmium batteries, and available with 10 or
20 amp charging circuits. The controller monitors,
displays and records re pump system information.
Metering
The controller provides display of incoming
AC power line voltages.
Total engine run time may be displayed.
Pressure is displayed in PSI or Bars in 1 psi in-
crements (0.1 bar). The controller is supplied
as standard with a 0-300 psi (0-20.7 bars)
stainless steel pressure transducer for fresh
water applications and optionally with a 0-600
psi (0-41.4 bars) pressure transducer.
Controllers can be ordered for copper corro-
sive applications.
Battery voltages and charging currents are
displayed on the main screen
Engine Control
The controller provides the following program-
mable engine control functions:
Sequential Start Time (On Delay) - 0-60 Sec-
onds
Minimum Run Time - 0-60 Minutes
Off Delay Time - 0-60 Minutes
Weekly Test Time/Duration/Frequency
AC Power Loss Start Delay Time - 5-300 Sec-
onds
Manual Stop Only - Yes/No
Operator Interface
The re pump controllers feature an operator inter-
face with user keypad. The interface monitors and
displays motor operating conditions, including all
alarms, events, and pressure conditions. All alarms,
events, and pressure conditions are displayed with a
Page view 1
1 2 3 4