Emerson CP200 Instruction Manual Page 6

  • Download
  • Add to my manuals
  • Print
  • Page
    / 12
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 5
CP200 Series
6
Secondary Seat™ Protection does not provide additional
overpressure protection in the event the secondary seat or
disk is damaged by debris or contamination in the pipeline,
or from conditions that would cause the regulator to go
wide-open. When selecting Secondary Seat Protection
option, it is recommended that:
Other additional overpressure protection methods be
added in the downstream system as discussed in the
Overpressure Protection section; and
A periodic downstream lock-up pressure test is done.
If lockup pressures are elevated above normal, that
indicates that the primary orice/seat or the disc are no
longer providing shutoff and that the Secondary Seat
Protection option is serving as the primary shutoff. The
regulator should then be maintained as discussed in the
Maintenance section of this manual.
Installation and Overpressure
Protection
!
WARNING
Personal injury or system damage may
result if this regulator is installed, without
appropriate overpressure protection, where
service conditions could exceed the limits
given on the regulator nameplate.
Regulator installations should be adequately
protected from physical damage.
The loading regulator vent should be kept open
to permit free ow of gas to the atmosphere.
Protect vent openings against entrance of
rain, snow, insects, or any other foreign
material that may plug the vent or vent line.
On outdoor installations, point the loading
regulator vent downward to allow condensate
to drain (see Figures 4 and 8). This minimizes
the possibility of freezing and of water or
other foreign materials entering the vent and
interfering with proper operation.
Under enclosed conditions or indoors,
escaping gas, such as in the case of a
ruptured diaphragm, may accumulate and be
an explosion hazard.
CAUTION
The CP200 Series regulators have an
outlet pressure rating lower than their inlet
pressure rating. If actual inlet pressure can
exceed the outlet pressure rating, outlet
overpressure protection is necessary.
However, overpressuring any portion of
the regulators beyond the limits in the
Specications section may cause leakage,
damage to regulator parts, or personal injury
due to bursting of pressure-containing parts.
Some type of external overpressure
protection should be provided if inlet pressure
will be high enough to damage downstream
equipment. Common methods of external
overpressure protection include relief valves,
monitoring regulators, shut-off devices, and
series regulation.
If the regulator is exposed to an
overpressure condition, it should be
inspected for any damage that may have
occurred. Regulator operation below these
limits does not preclude the possibility of
damage from external sources or from debris
in the pipeline.
The CP200 Series is an internally registered
pressure reducing regulator and has
outlet pressure ratings lower than the inlet
pressure ratings. Complete downstream
overpressure protection is needed if the
actual inlet pressure exceeds the outlet
pressure rating.
General Installation Instructions
Before installing the regulator:
Check for damage, which might have occurred
during shipment.
Check for and remove any dirt or foreign material, which
may have accumulated in the regulator body.
Blow out any debris, dirt or copper sulfate in any copper
tubing and the pipeline.
Apply pipe compound to the external threads of the pipe
before installing the regulator.
Ensure gas ow through the regulator is in the same
direction as the arrow on the body. “Inlet” and “Outlet”
connections are clearly marked.
Installation Location
The installed regulator should be adequately protected from
vehicular trafc and damage from other external sources.
Figure 4. CP200 Series Regulator Installed with a Type 289H
Relief Valve for High Capacity Relief
PROTECT VENT PIPE
WITH RAIN CAP
TYPE 289H
RELIEF VALVE
TYPE 67CP/CPR
VENT POINTED DOWN
TYPE CP200
REGULATOR