LIEBERT
®
APM
3-PHASE UPS: 15-90KVA/KW, 60HZ, 208-600VAC, SINGLE & DUAL INPUT - SITE PLANNING DATA
BATTERY
NOTES
1. Install in accordance with national and local electrical codes.
2. Input and bypass must share the same single source.
3. A neutral is required from the system AC input source.
A full capacity neutral conductor is recommended.
Grounding conductors are recommended.
4. UPS system input and output cables must be run
in separate conduits.
5. Control wiring must be run in separate conduits.
6. Optional 54 pole, 225A for 45kVA frame only or
optional 54 pole, 400A for 90kVA frame only.
7. Transformer available 480V or 600V input.
UPS CABINET
* SYSTEM
AC INPUT
4 WIRE + GRD
(OPTIONAL)
54 POLE
SEE NOTE 6
AC OUTPUT
208V
4 WIRE + GND
STATIC BYPASS
MBB
MIBBIB
BYPASS DISTRIBUTION CABINET
(Optional; see Note 7)
UAM01004
Rev. 0
Field-supplied wiring
BIB Bypass Isolation Breaker
MBB Maintenance Bypass Breaker
MIB Maintenance Isolation Breaker
* External Overcurrent Protection by others
The UPS must be fed from a solidly
grounded wye or delta AC source. Not for
use with impedance-grounded systems,
corner-grounded or high leg delta sys-
tems. For these applications, an isolation
transformer must be installed between
the AC feed and the UPS.
Page view 0
1 2 3 4 5 6 7 8

Summary of Contents

Page 1

1LIEBERT® APM™ 3-PHASE UPS: 15-90KVA/KW, 60HZ, 208-600VAC, SINGLE & DUAL INPUT - SITE PLANNING DATABATTERYNOTES1. Install in accordance with nati

Page 2 - Notes for Tables

2Notes for Tables 1. Nominal (Nom) current is based on full rated output load at nominal input voltage.2. Maximum (Max) current (125% of nominal) is s

Page 3

3Table 2 Site Planning Data - 15-90kVA, 60Hz, 480VAC, Single InputUPS Rating Voltage AC Input Battery AC Output Mechanical DataSystem OCPD(45 and 90 k

Page 4

4Table 4 Site Planning Data - 15-90kVA, 60Hz, 208VAC, Dual InputUPSRating Voltage AC Rectifier Input208VACBypass Input Battery AC Output Mechanical Da

Page 5

5Table 6 Site Planning Data - 15-90kVA, 60Hz, 600VAC, Dual InputUPS Rating Voltage AC Input208VACBypass Input Battery AC Output Mechanical DataInput C

Page 6

6 Table 9 UPS currents and terminals—Output 208VUnit Rating Nom. Output Current OCP Device Rating Bolt Size 75°C Wire Current tot WireMaximum Recommen

Page 7 - Internal Battery

7General SpecificationsINPUTVoltage 208/120, 220/127VAC, 50/60Hz, 3-phase, 4-wire plus groundVoltage Range Without Derating +15%, -20%Frequency Range

Page 8

8© 2010 Liebert CorporationAll rights reserved throughout the world. Specifications subject to change without notice.® Liebert is a registered tradema