1LIEBERT® APM™ 3-PHASE UPS: 15-90KVA/KW, 60HZ, 208-600VAC, SINGLE & DUAL INPUT - SITE PLANNING DATABATTERYNOTES1. Install in accordance with nati
2Notes for Tables 1. Nominal (Nom) current is based on full rated output load at nominal input voltage.2. Maximum (Max) current (125% of nominal) is s
3Table 2 Site Planning Data - 15-90kVA, 60Hz, 480VAC, Single InputUPS Rating Voltage AC Input Battery AC Output Mechanical DataSystem OCPD(45 and 90 k
4Table 4 Site Planning Data - 15-90kVA, 60Hz, 208VAC, Dual InputUPSRating Voltage AC Rectifier Input208VACBypass Input Battery AC Output Mechanical Da
5Table 6 Site Planning Data - 15-90kVA, 60Hz, 600VAC, Dual InputUPS Rating Voltage AC Input208VACBypass Input Battery AC Output Mechanical DataInput C
6 Table 9 UPS currents and terminals—Output 208VUnit Rating Nom. Output Current OCP Device Rating Bolt Size 75°C Wire Current tot WireMaximum Recommen
7General SpecificationsINPUTVoltage 208/120, 220/127VAC, 50/60Hz, 3-phase, 4-wire plus groundVoltage Range Without Derating +15%, -20%Frequency Range
8© 2010 Liebert CorporationAll rights reserved throughout the world. Specifications subject to change without notice.® Liebert is a registered tradema