How to Assign a MODBUS Address Digital Inputs • 13
9 Digital Inputs
The XEV22D comes with two (2) digital inputs: a
voltage-free input and a high voltage input; both can
be configured as cooling call. In this way the cooling
signal can come from the controllers with direct load
outputs or via the controllers with voltage-free out-
puts. One of these inputs must be configured as the
cooling call.
10 Forced Opening
If necessary, change the FOP parameter to force
the valve to open. For example, if FOP is set to 50
(FOP = 50), the valve will be opened at half of full
scale. To disable this function, set the
FOP to default
value (FOP = not used). The valve opening is en-
abled only when CCL digital input is enabled.