Micro MotionTMModel 3700 Transmitter(9-Wire) orModel 3350 PeripheralInstallation Instructions forField-MountQuick Reference GuideP/N 3300996, Rev. CAp
9STEP 6. Connecting the Model 3700 to the sensorIf you are installing the Model 3350 applications peripheral, this step is not required. To connect th
10For information on your sensor’s junction box terminals, see the sensor installation manual or Micro Motion’s 9-Wire Flowmeter Cable Preparation and
113. Connect wires to terminals 9 and 10 on the gray terminal strip. See Figure 8, page 8.A user-supplied switch may be installed in the power supply
Micro MotionTMMicro Motion EuropeEmerson Process ManagementWiltonstraat 303905 KW VeenendaalThe NetherlandsT +31 (0) 318 495 670F +31 (0) 318 495 689M
1BEFORE YOU BEGINThis quick reference guide explains basic installation guidelines for mounting the Micro Motion® Model 3350/3700 applications platfor
2European installationsThis Micro Motion product complies with all applicable European directives when properly installed in accordance with the instr
3STEP 1. Choosing a locationChoose a location for the transmitter based on the requirements described below.Environmental requirementsInstall the Mode
4Figure 2. Dimensions – face viewFigure 3. Dimensions – top view4 x 5/16-inch (9 mm)diameterDisplay cover can berotated as neededMounting bracket canb
5STEP 2. Preparing conduit openings for ATEX Zone 1If the Model 3350/3700 carries an ATEX Zone 1 approval:1. Remove thread protectors from conduit ope
6STEP 4. Mounting the applications platformFor flat-surface mounting, see Figure 5.For pole mounting, see Figure 6.Figure 5. Mounting to a flat surfac
7STEP 5. Connecting input and output wiringFigure 7 shows the location of the wiring terminals on the Model 3350/3700.Figure 7. Wiring terminals1. Use
8Figure 8. Wiring terminal labelsTable 1. Input/output wiring terminalsTerminal number Designation1 – 2 + Primary 4–20 mA output3 – 4 + Secondary 4–20