N1 ATEX Type n
Certificate: BAS01ATEX3304X
Standards: EN 60079-0: 2012, EN 60079-15: 2010
Markings:
II 3 G Ex nA IIC T5 Gc, (-40 °C T
a
+85 °C), V
max
= 45V
Special Condition for Safe Use (X):
1. The equipment is not capable of withstanding the 500 V insulation test
required by clause 6.5 of EN 60079-15:2010. This must be taken into account
when installing the equipment.
Note
RTD Assembly is not included with the 3051SFx Type n Approval.
International
E7 IECEx Flameproof and Dust
Certificate: IECEx KEM 08.0010X (Flameproof)
Standards: IEC 60079-0:2011, IEC 60079-1: 2007, IEC 60079-26:2006
(3051SFx models with RTD are certified to IEC 60079-0:2004)
Markings: Ex d IIC T6…T4 Ga/Gb, T6(-60 °C
T
a
+70 °C),
T5/T4(-60 °C
T
a
+80 °C)
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm. Installation, maintenance and use
shall take into account the environmental conditions to which the diaphragm
will be subjected. The manufacturer’s instructions for installation and
maintenance shall be followed in detail to assure safety during its expected
lifetime.
2. For information on the dimensions of the flameproof joints the manufacturer
shall be contacted.
Certificate: IECEx BAS 09.0014X (Dust)
Standards: IEC 60079-0:2011, IEC 60079-31:2008
Markings: Ex ta IIIC T 105 °C T
500
95 °C Da, (-20 °C T
a
+85 °C), V
max
= 42.4V
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the
enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which
maintain the ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient
temperature range of the apparatus and capable of withstanding a 7 J impact
test.
4. The 3051S SuperModule must be securely screwed in place to maintain the
ingress protection of the enclosure.
Temperature class Process temperature
T6 -60 °C to +70 °C
T5 -60 °C to +80 °C
T4 -60 °C to +120 °C