Emerson GXT4 Datasheet Page 4

  • Download
  • Add to my manuals
  • Print
  • Page
    / 8
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 3
4
Liebert
®
GXT4™ UPS 5 and 6kVA models are true on-line
UPS systems that provide internal batteries and dual
output voltage. They are an ideal fit for applications
where the power requirements are demanding such as
network closets or small equipment racks.
Adaptable Design
For installation exibility, the Liebert GXT4 UPS 5 and 6kVA
models allow you to choose from several different wiring
congurations made possible by the use of removable
power distribution boxes (PODs) that simply plug into the
rear of the UPS. The standard box provides terminal blocks
for hardwired input and output connections. An optional
hardwire version that includes a maintenance bypass is
also available.
When the ease of plug-and-play power connections is
desired, optional versions of the power distribution box
convert Liebert GXT4 UPS 5 and 6kVA units to a cord-type
input with receptacles for output distribution, and also
offers maintenance bypass capability that allows hot-
swapping of the entire UPS without interruption of power
to the connected load.
The UPS has as adaptable dual inverter design, capable of
providing output voltages of 240/120, 208/120, 230/115,
220/110, or 200/100 and an output power factor of 0.8.
5 and 6kVA Models Offer True
On-Line Power In A Convenient
Rack Conguration
8kVA and 10kVA Models
Provide Even More Power
The Liebert
®
GXT4™ UPS 8 and 10kVA units offer a flexible
solution for protecting rack-mount equipment, including
VoIP and PoE.
Specifically designed for use with the new generation of
high power switches, these compact UPS systems pack
8kVA (7.2kW) or 10kVA (9kW) of power into a 6U rack/
tower package with flexible output voltage and optional
output distribution. The UPS includes built-in, replaceable
batteries for up to 5-8 minutes of runtime at full load
depending on model.
Adaptable Design
The UPS has a dual inverter design, capable of providing 5 output
voltages of 240/120, 208/120, 230/115, 220/110, or 200/100
and an output power factor of 0.9. The 6U size is the smallest for
208/120 selectable voltage in the 8-10kVA model range.
The unit features integrated internal automatic and manual
maintenance bypass, power module, battery modules, and
optional plug-and-play distribution plates.
The standard 8 and 10kVA models include terminal blocks
for hardwired connections of both input and output. Optional
power distribution modules (PODs) are available to add output
receptacles to the rear panel of the unit.
Hot-Swappable Operation
Liebert GXT4 UPS 8 and 10kVA units feature three bays for one
power module and two battery modules. The chassis contains
a bypass switch that allows all modules to be removed without
powering down the connected load.
UPS is hardwire input/output
with maintenance bypass and
includes no POD standard.
Optional PODs available
5 and 6 kVA Model shown in rack mount position
6 kVA Model shown in tower orientation
8-10 kVA Models
Page view 3
1 2 3 4 5 6 7 8

Comments to this Manuals