Emerson T1 Datasheet Page 25

  • Download
  • Add to my manuals
  • Print
  • Page
    / 32
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 24
General Technical Specifications
Part Number Edco TCS-T1S
Operating Voltage 170 VDC
Clamping Voltage 211 VDC
Operating Current 1A
Total Peak Surge Current* 40,000 A
Frequency Range 0 to 55MHz
Insertion Loss < 0.1 dB at 55 MHz
SPD Technology SAD / GDT
Connection Type Hardwire Lugs or RJ-45
Operating Temperature -40°C to +85°C
Dimensions (Inches) 2H x 3W x 1.5D
Weight 5 oz
Certifications UL 497B
*Based on component specifications for all T1 lines.
Features
Uses bipolar Silicon Avalanche Diode to
provide nondegrading protection
Provides unparalleled performance in a
compact, modular design
Offers RJ or hardwire connection
capabilities to provide installation flexibility
Comes complete with ring terminals
and a male/male RJ-45 cable to make
installation easy
1 year warranty
Edco TCS-T1 Series
T1 Line Protection Against Damaging Transients
Protection of your vital T1 lines should be part of the overall power protection plan
for your facility. The Edco TCS-T1 Series provides you state-of-the-art protection in
a small package.
T1 lines need protection from direct and indirect lightning, as well as power
disturbances from nearby AC lines. The Edco TCS-T1 Series prevents T1 line
disturbances by providing a level of protection typically not provided by the
telephone company.
The Edco TCS-T1 Series devices combine highly reliable, nondegrading Silicon
Avalanche Diode (SAD) technology, along with high energy gas tube protection.
This technology combination leverages the best aspects of each protection
method in a single, reliable design to ensure optimal performance.
The Edco TCS-T1 Series features two models with different clamping voltages.
Both the Edco TCS-T1S and the Edco TCS-T1DS support in-line connections via
hardwire lugs or standard RJ-45 ports.
Part Number Edco TCS-T1DS
Operating Voltage 8 VDC
Clamping Voltage 13 VDC
Operating Current 1A
Total Peak Surge Current* 40,000 A
Frequency Range 0 to 55MHz
Insertion Loss < 0.1 dB at 55 MHz
SPD Technology SAD / GDT
Connection Type Hardwire Lugs or RJ-45
Operating Temperature -40°C to +85°C
Dimensions (Inches) 2H x 3W x 1.5D
Weight 5 oz
Certifications UL 497B
23
Data/Signal Line Protection
Page view 24
1 2 ... 20 21 22 23 24 25 26 27 28 29 30 31 32