Hazardous Area Oxymitter 4000
http://www.raihome.com
Section 7 HART/AMS
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-1
HART Communicator Signal Line Connections . . . . . . . page 7-2
HART Communicator PC Connections . . . . . . . . . . . . . . . page 7-4
Off-Line and On-Line Operations . . . . . . . . . . . . . . . . . . . page 7-4
Logic I/O Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-5
HART/AMS Menu Tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-5
HART Communicator O
2
Cal Method . . . . . . . . . . . . . . . . page 7-9
Defining a Timed Calibration via HART . . . . . . . . . . . . . . page 7-10
D/A Trim Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-11
OVERVIEW
The HART Communicator is a handheld communications interface device. It
provides a common communications link to all microprocessor-based
instruments that are HART compatible. The handheld communicator contains
an 8 x 21 character liquid crystal display (LCD) and 25 keys. A pocket-sized
manual, included with the HART Communicator, details the specific functions
of all the keys.
To interface with the Hazardous Area Oxymitter 4000, the HART
Communicator requires a termination point along the 4-20 mA current loop
and a minimum load resistance of 250 ohms between the communicator and
the power supply.
The HART Communicator accomplishes its task using a frequency shift
keying (FSK) technique. With the use of FSK, high-frequency digital
communication signals are superimposed on the Hazardous Area Oxymitter
4000's 4-20 mA current loop. The HART communicator does not disturb the
4-20 mA signal, since no net energy is added to the loop.
The HART Communicator may be interfaced with a personal computer (PC),
providing that special software has been installed. To connect the HART
Communicator to a PC, an interface adapter is required. Refer to the proper
HART Communicator documentation in regard to the PC interface option.
The HART option is not protected by energy limiting barriers. It must not be interfaced from
within the hazardous area. The 4-20 mA cables should be routed and the connections made
outside the hazardous area. Note that this is the case even when using the intrinsically safe
version of the handheld communicator