Large Systems iCOM Microprocessor Environmental Training and Service Manual TM-10098: Rev. 02/06

Page 2 - Training & Service

iCOM Control Training and Service Manual The integral (I) term is determined by two things: the difference between the return air temperature and cont

Page 3

iCOM Control Training and Service Manual MISMATCH 130 UNIT CODE 16 MISMATCH " Alarm yes yes no 131 UNIT CODE 17 MISMATCH " Alarm yes yes

Page 4 - Table of Contents

iCOM Controls Training and Service Manual Chapter 3 iCOM Control Board Connections Introduction This section describes the basic connection poi

Page 5

iCOM Control Training and Service Manual 101 LCD Display Board The Advanced and Advanced with Graphics LCD display board is mounted to the system unit

Page 6

iCOM Controls Training and Service Manual 102 Control Board DIP Switches and Plug Connectors This section deals with the 20 plug connections and the t

Page 7 - Control Programs

iCOM Control Training and Service Manual iCOM Control Board DIP Switch #2 Settings Connector Input/ Output Type SettingP7-1 (+)/ P7-2 (-) NTC Thermi

Page 8

iCOM Controls Training and Service Manual iCOM Control Board Jumper Settings Jumper Type SettingP19 Watchdog * On: Shunt on Pins 1 & 2 Off: No Sh

Page 9 - Proportional (P) Control

iCOM Control Training and Service Manual Large Display Jumper Settings Jumper Type SettingP3 Watchdog * Shunt on Pins 1 & 2 P4 Manual Contrast

Page 10

iCOM Controls Training and Service Manual Small Display Jumper Settings Jumper Type SettingP4 Manual Contrast (Rev. 2 only) * Shunt on Pins 2 & 3

Page 11

iCOM Control Training and Service Manual DS Systems: P3: Not Used P4: 24 VAC Power P4-1: Fuse 1 (24 VAC) P4-3: Fuse 3 (24 VAC) P4-2: Fuse 2 (2

Page 12 - Temperature Control

iCOM Controls Training and Service Manual P22: Glycool Valve (Std. Pressure Actuator) P22-1: 24 VAC Out (Close Q18) P22-4: DCV Signal P22-2: DCV Sign

Page 13

iCOM Controls Training and Service Manual A suggested tuning procedure is as follows: 1. Initially adjust the integral and derivative settings to 0%

Page 14

iCOM Control Training and Service Manual P38: Smoke Detector P38-1: 24 VAC Out SDC) P38-3: 24 VAC (RAD1) P38-2: E4 (SDC) P38-4: no connection P39

Page 15

iCOM Controls Training and Service Manual P67: Temperature/ Humidity Sensors P67-1: P16-3: P67-6: P16-4: P65: Site Monitoring Signals – No

Page 16

iCOM Control Training and Service Manual 111 Fuse Board Layout: All Units This section deals with the seven (7) plug connectors on the fuse board. Th

Page 17

iCOM Controls Training and Service Manual 112 Temperature/ Humidity Board: All Units This section deals with the single plug connection located on the

Page 18

iCOM Control Training and Service Manual NOTES 113

Page 19

iCOM Controls Training and Service Manual 114 Chapter 4 General Troubleshooting Data * Basic Operation of the Opto and Triac * Troublesho

Page 20

iCOM Control Training and Service Manual 115 The temperature sensor senses a rise in temperature. The rise is transmitted to the Central Processing

Page 21

iCOM Controls Training and Service Manual 116 BASIC OPERATION OF THE TRIAC To better understand the operation of the triac, we need to look at the mo

Page 22 - Staged Electric Reheat

iCOM Control Training and Service Manual 117 The triacs that Liebert uses are standard in the industry and are rated at a 2-amp capacity. You can che

Page 23

iCOM Controls Training and Service Manual 118 Basic Operation of the Opto-Isolator The purpose of the opto-isolator is to provide isolation of two vo

Page 24

iCOM Control Training and Service Manual Temperature Control Operations and Charts The temperature proportional control band value is divided into

Page 25 - Humidity Control

iCOM Control Training and Service Manual 119 Troubleshooting the Output Opto-Isolator The opto-isolator IC chips used in these circuits are the H11J

Page 26

iCOM Controls Training and Service Manual 120 Troubleshooting the Input Opto-Isolator The opto-isolator IC chips used in these circuits are the H11AA

Page 27 - Humidifier Operation

iCOM Control Training and Service Manual 121 Microprocessor Control Board: Typical Location othe Opto-Isolators and Triacs Input Opto

Page 28

iCOM Controls Training and Service Manual Note: Use Pin 5 on the input opto-isolator with reference to the V- terminal for voltage check. The voltage

Page 29

iCOM Control Training and Service Manual iCOM Diagnostics / Service Mode Program The iCOM controller has a valuable tool built into software under t

Page 30

iCOM Controls Training and Service Manual Basic Troubleshooting Steps: Example: Unit load is not energizing. Programming: 1. Read and record al

Page 31 - Systems

iCOM Control Training and Service Manual 2. If the programming is correct and the output opto-isolator is functioning properly but the load device is

Page 32

iCOM Controls Training and Service Manual Moisture Content Charts The following charts show moisture content of various levels of relative humidity f

Page 33

iCOM Control Training and Service Manual Moisture Content at Temperature = 80°F (26.7ºC) RH Grains Per Cu Ft Grains Per Lb. 35 3.864 53.59368 36

Page 34

iCOM Controls Training and Service Manual Moisture Content at Temperature = 79°F (26.1ºC) RH Grains Per Cu Ft Grains Per Lb. 35 3.7485 51.9917 3

Page 35 - Caution:

iCOM Controls Training and Service Manual The temperature controller deactivates the second stage of cooling (lag compressor) when the return air temp

Page 36 - Additional Programs

iCOM Control Training and Service Manual Moisture Content at Temperature = 78°F (25.6ºC) RH Grains Per Cu Ft Grains Per Lb. 35 3.633

Page 37

iCOM Controls Training and Service Manual Moisture Content at Temperature = 77°F (25.0ºC) RH Grains Per Cu Ft Grains Per Lb. 35 3.521

Page 38

iCOM Control Training and Service Manual Moisture Content at Temperature = 76°F (24.4ºC) RH Grains Per Cu Ft Grains Per Lb. 35 3.41215

Page 39 - Next Maintenance Calculation

iCOM Controls Training and Service Manual Moisture Content at Temperature = 75°F (23.9ºC) RH Grains Per Cu Ft Grains Per Lb. 35 3.3068

Page 40

iCOM Control Training and Service Manual Moisture Content at Temperature = 74°F (23.3ºC) RH Grains Per Cu Ft Grains Per Lb. 35 3.20355

Page 41

iCOM Controls Training and Service Manual Moisture Content at Temperature = 73°F (22.8ºC) RH Grains Per Cu Ft Grains Per Lb. 35 3.10345

Page 42 - Networking and Functions

iCOM Control Training and Service Manual Moisture Content at Temperature = 72°F (22.2ºC) RH Grains Per Cu Ft Grains Per Lb. 35 2.9988

Page 43 - The Basics for Hardware:

iCOM Controls Training and Service Manual Moisture Content at Temperature = 71°F (21.7ºC) RH Grains Per Cu Ft Grains Per Lb. 35 2.91165

Page 44

iCOM Control Training and Service Manual Moisture Content at Temperature = 70°F (21.1ºC) RH Grains Per Cu Ft Grains Per Lb. 35 2.81925

Page 45 - Setting Parameters

iCOM Controls Training and Service Manual Moisture Content at Temperature = 69°F (20.6ºC) RH Grains Per Cu Ft Grains Per Lb. 35 2.7293

Page 46 - Unit No. 2

iCOM Control Training and Service Manual 2 Stage Compressorized Cooling – With Dead Band Temp Set Point: 70°F Proportional Band: 8°F Dead Band: 2°F

Page 47

iCOM Control Training and Service Manual Moisture Content at Temperature = 68°F (20.0ºC) RH Grains Per Cu Ft Grains Per Lb. 35 2.64985

Page 48

iCOM Controls Training and Service Manual Moisture Content at Temperature = 67°F (19.4ºC) RH Grains Per Cu Ft Grains Per Lb. 35 2.5578

Page 49 - Teamwork

iCOM Control Training and Service Manual Moisture Content at Temperature = 66°F (18.9ºC) RH Grains Per Cu Ft Grains Per Lb. 35 2.4759

Page 50 - Teamwork Mode 2

iCOM Controls Training and Service Manual Moisture Content at Temperature = 65°F (18.3ºC) RH Grains Per Cu Ft Grains Per Lb. 35 2.39575

Page 51 - Standby & Cascade

iCOM Control Training and Service Manual 143 Suction Transducer Information (Codes A124-A128) % psig psia

Page 52

iCOM Controls Training and Service Manual Digital Scroll High Temperature Sensor Chart NTC (Code S606 and S608) 144

Page 53 - Chapter 2

iCOM Control Training and Service Manual Unit Code Description The iCOM controller uses a system parameters auto configuration methodology. The unit

Page 54

iCOM Controls Training and Service Manual Troubleshooting Checklist 1. Check the obvious before beginning troubleshooting. A. Be sure that a r

Page 55 - Icon Key Name Function

iCOM Control Training and Service Manual Glossary of Unit and System Parameters User Menu Code Setpoints Type U102 Temperature setpoint Unit U103

Page 56

iCOM Controls Training and Service Manual Code Display Setup Type U401 Language Display U402 Date Unit U403 Time Unit U404 Temperature Indication

Page 57 - Programming Functions

iCOM Controls Training and Service Manual and will be supplied with an electrical cylinder unloader valve. The electrical solenoid valve used to unlo

Page 58 - Menu Parameters Names

iCOM Control Training and Service Manual Code Service contacts Type U703 Address line 1 System U704 Address line 2 System U705 Address line 3

Page 59 - Display

iCOM Controls Training and Service Manual Fan Settings Type S013 Number of starts Unit S014 Working hours Unit S015 Average working time Unit

Page 60

iCOM Control Training and Service Manual S063 Actual bonus Unit El. Heater 3 Settings Type S068 Number of starts Unit S069 Working hours Unit S

Page 61 - Menu Parameters

iCOM Controls Training and Service Manual S338 Status Filter Unit S339 Status Customer Input 1 Unit S340 Status Customer Input 2 Unit S341 Status C

Page 62

iCOM Control Training and Service Manual S614 Calibrated Temp. Sensor A Unit S615 Humidity Sensor A Unit S616 Calibrated Humidity Sensor A Unit

Page 63

iCOM Controls Training and Service Manual S407 Electrical Unit S408 Hot water On/Off Unit S409 Hot gas Unit S410 3P actuator runtime Unit S411 3

Page 64

iCOM Control Training and Service Manual A117 Low pressure threshold Phase 1 Unit A118 Low pressure threshold Phase 2 Unit A124 LP1 sensor 0% =

Page 65

iCOM Controls Training and Service Manual Glossary of Terms Address: A pattern of characters that identifies a unique storage location Algorithm:

Page 66

iCOM Control Training and Service Manual CPU: Central Processing Unit; the part of a computer system that contains the main storage, arithmetic unit

Page 67

iCOM Controls Training and Service Manual Impedance: Opposition that a circuit offers to the flow of current through it, measured in Ohms Input: A

Page 68 - Service Menu Parameters

iCOM Control Training and Service Manual 4 Stage Compressorized Cooling – No Dead Band Temp Set Point: 70°F Proportional Band: 8°F 70 71

Page 69

iCOM Control Training and Service Manual Prefill: The period of time between when the water begins to fill the pan and the humidifier lamps turn on

Page 70

iCOM Controls Training and Service Manual Computer and Network Terms Agent: A program that performs some information gathering or processing task in

Page 71

iCOM Control Training and Service Manual Ethernet: A local-area network (LAN) architecture developed by Xerox Corporation in cooperation with DEC and

Page 72

iCOM Controls Training and Service Manual • wide-area networks (WANs): The computers are farther apart and are connected by telephone lines or radio

Page 73

iCOM Control Training and Service Manual There are a variety of standard protocols from which programmers can choose. Each has particular advantages

Page 74

iCOM Controls Training and Service Manual Understanding IP Addressing: Every computer that communicates over the Internet is assigned an IP address t

Page 75

iCOM Control Training and Service Manual 165 Network Information Commonly known as: Network wire, Ethernet cable, Cat5 cable, the information followi

Page 76

iCOM Controls Training and Service Manual 166 Switches perform the same mechanical function, but they also include software inside that allows communi

Page 77

iCOM Control Training and Service Manual How To Use The Schematics As you look at the outside edge of the electrical schematic (drawing), you will se

Page 78

iCOM Controls Training and Service Manual Electrical Schematics 182769 Liebert DS iCOM Global Control 8 - 12 Ton 182770 Liebert DS iCOM Global Contro

Page 79

iCOM Controls Training and Service Manual The example below is based on a temperature set point of 70°F with a control band length of 4°F, which is ½

Page 80

iCOM Control Training and Service Manual Notes 169

Page 81

iCOM Control Training and Service Manual As the return air temperature increases Cooling 1, lead compressor unloaded, is activated at 72°F or ½ of the

Page 82

iCOM Controls Training and Service Manual Optional Dual Compressor Digital Scroll Operation 2 compressor operation C1 C2Start/ st

Page 83

iCOM Control Training and Service Manual iCOM Training & Service Manual 1

Page 84

iCOM Control Training and Service Manual temperature is at least 8°F below the return air temperature, or 3°F lower than the return air temperature fo

Page 85 - Advanced Menu Parameters

iCOM Controls Training and Service Manual Glycool at 50% Capacity – No Dead Band Temp Set Point: 70° Proportional Band: 8° 70

Page 86

iCOM Control Training and Service Manual 2-Stage or 4-Stage control method. If the chilled water temperature is not cold enough the valve control ban

Page 87

iCOM Controls Training and Service Manual of the heating proportional band. The third electric heating stage activates when the return air temperatur

Page 88

iCOM Control Training and Service Manual 3 Stage Electric Reheat – With Dead Band Temp Set Point: 70°F Proportional Band: 8°F Dead Band: 2°F 65

Page 89

iCOM Controls Training and Service Manual Humidity Control Humidification and/ or Dehumidification Required, in Percent (%) The humidity control pro

Page 90

iCOM Control Training and Service Manual Temperature Set PointHumidity Set PointHumidity Proportional Band = 6%Content Le

Page 91

iCOM Controls Training and Service Manual Relative Humidity Control Relative humidity control is based on the humidity content in the return air. The

Page 92

iCOM Control Training and Service Manual Infrared Humidification – No Dead Band Humid Set Point: 50% Proportional Band: 8% 45 46 47

Page 93

iCOM Controls Training and Service Manual Infrared Humidification – With Dead Band Humid Set Point: 50% Proportional Band: 8% Dead Band: 2% 45

Page 94

iCOM Controls Training and Service Manual Disclaimer of Warranties and Limitations of Liabilities The authors and editors have taken every precautio

Page 95

iCOM Control Training and Service Manual If the off time is less than 15 hours (or user programmed value) the pre-fill program is bypassed and the inf

Page 96

iCOM Controls Training and Service Manual Dehumidification Operation The Relative Humidity control program is used to illustrate the dehumidification

Page 97

iCOM Control Training and Service Manual Note: in the above example that the control band begins at the 50% humidity set point and has a length of 4%

Page 98

iCOM Controls Training and Service Manual The humidity controller activates the first stage of dehumidification operation when the return air humidity

Page 99

iCOM Control Training and Service Manual When the return air humidity level decreases to 52%RH or 50% of the dehumidification control band the second

Page 100

iCOM Controls Training and Service Manual dehumidification process. The end user can choose to select from the following selections: Parameter Opera

Page 101 - Chapter 3

iCOM Control Training and Service Manual Additional Programs Start The unit fan is activated. The unit can be switched on/ off from 2 inputs: 1. R

Page 102 - LCD Display Board

iCOM Controls Training and Service Manual Fan Alarm / Fan settings The fan operation is controlled by two (2) digital devices: the Loss of Airflow di

Page 103 - Unit Mounted Control Board

iCOM Control Training and Service Manual The Startup and Freeze Protection Program The sequence for the call for cooling with the progr

Page 104

iCOM Controls Training and Service Manual during the second time frame the cooling process locks off and will require a power off sequence. Next Mai

Page 105

iCOM Control Training and Service Manual Table of Contents Chapter 1: Temperature/ Humidity Control 6Temperature Control Types 6Intelligent Control

Page 106

iCOM Control Training and Service Manual The control always takes the component with the most on/ off (cycling) as the reference component, which aski

Page 107

iCOM Controls Training and Service Manual Starts per Day Optimum: the number of individual component starts that is considered as good or optimum. T

Page 108 - DS Systems:

iCOM Control Training and Service Manual Freecooling and Dual cooling will operate in the same manner as chilled water with the supervision of the Sup

Page 109

iCOM Controls Training and Service Manual The Basics for Cooling Unit Placement: Installation instructions are found in the product manuals for the Co

Page 110

iCOM Control Training and Service Manual 6. Each set of unit control boards must be set up individually, then connected to the network switch and che

Page 111

iCOM Controls Training and Service Manual Setting Parameters Example: 2 Units with Small Display’s All Network parameters are viewed and program

Page 112 - Fuse Board Layout: All Units

iCOM Control Training and Service Manual Example: 2 Units, One Large Display and One Small Display All Network parameters are viewed and programmed

Page 113

iCOM Controls Training and Service Manual Example: Large Wall Display and Five Units with Small Displays All Network parameters are viewed and prog

Page 114

iCOM Control Training and Service Manual Example: 4 Units in 2 Groups with 2 Large Displays All Network parameters are viewed and programmed using

Page 115 - Chapter 4

iCOM Controls Training and Service Manual Teamwork Teamwork Modes Teamwork is the ability to group unit functionality, while connected in a network,

Page 116 - Isolation

iCOM Controls Training and Service Manual Chapter 2: Programming Functions 52Programming Functions 52iCOM Display Components and Functions 53iCOM K

Page 117 - BASIC OPERATION OF THE TRIAC

iCOM Control Training and Service Manual Teamwork Mode 2 In teamwork mode 2 all system parameters are shared equally as in teamwork mode 1. The lead

Page 118

iCOM Controls Training and Service Manual The Lead/ Lag function may be used in the either the No Teamwork Mode, in Teamwork 1 Mode and in Teamwork 2

Page 119

iCOM Control Training and Service Manual Notes: 51

Page 120

iCOM Controls Training and Service Manual Chapter 2 Programming Functions The standard iCOM control is supplied with a front panel mounted small d

Page 121

iCOM Control Training and Service Manual iCOM Display Components and Functions The large display is shown for reference. The keypad and LEDs are ide

Page 122

iCOM Controls Training and Service Manual iCOM Keyboard Layout: Icon Key Name Function On/ Off Key Controls the operation state of the unit. Ala

Page 123

iCOM Control Training and Service Manual iCOM Display Symbols/ Icons hot water el. heaters dehum humhornfan compressor freeco

Page 124

iCOM Controls Training and Service Manual Programming Functions Status Display The unit display will show the unit operational mode(s), return air te

Page 125

iCOM Control Training and Service Manual Menu Screens ICON Symbols Menu Parameters Names Level 1: User Level 2: Service Level 3: Advanced Reada

Page 126

iCOM Controls Training and Service Manual User Menu Icons and Descriptions: Icon Name Descriptions Available Display °C/ °F % RH SET Set Points To

Page 127 - Moisture Content Charts

iCOM Control Training and Service Manual Unit Control Board: Opto-Isolator/ Triac Legends 121iCOM Diagnostics/ Service Mode Programs 123Basic Trouble

Page 128

iCOM Control Training and Service Manual Service Menu Icons and Descriptions: Icon Name Descriptions Available Display °C/ °F % RH SET Set Points T

Page 129

iCOM Controls Training and Service Manual Advanced Menu Icons and Descriptions: Icon Name Descriptions Available Display Factory Settings Factory c

Page 130

iCOM Control Training and Service Manual User Menu: Set Point Parameters U100 series Menu Line Parameter Default Range U101 Password - - U102

Page 131

iCOM Controls Training and Service Manual User Menu: Graphics Parameters Parameter Default Range System Temperature Time Scale 24 Hours 8, 32 min

Page 132

iCOM Control Training and Service Manual User Menu: Set Alarm Parameters U200 series Menu Line Parameter Default Range U201 Password - - U202

Page 133

iCOM Controls Training and Service Manual User Menu: Sensor Data U300 series: Page 1 of 2 Menu Line Parameter Time/ Value U313 Daily High Tempert

Page 134

iCOM Control Training and Service Manual User Menu: Total Run Hours Parameters U500 series Menu Line Parameter Range (Hours) U501 - Actual U502

Page 135

iCOM Controls Training and Service Manual User Menu: Service Contacts U700 series Menu Line Parameter Range U701 U702 U703 Address Line 1

Page 136

iCOM Control Training and Service Manual Service Menu Parameters The Service menu display allows the user to customize the various unit settings for s

Page 137

iCOM Controls Training and Service Manual Service Menu: Set Point Parameters S100 series: Page 2 of 2 Menu Line Parameter Default Range S112 Pass

Page 138

iCOM Controls Training and Service Manual Chapter 1 Temperature and Humidity Control Programs This section provides details on how your Liebert iC

Page 139

iCOM Control Training and Service Manual Service Menu: Standby Setting / Lead-lag Parameters S500 series Menu Line Parameter Default Range S501

Page 140

iCOM Controls Training and Service Manual Service Menu: Fan Settings Maintenance / Wellness Parameters: Page 2 of 8 Menu Line Parameter Default R

Page 141

iCOM Control Training and Service Manual Service Menu: Compressor 2 Settings Maintenance / Wellness Parameters: Page 4 of 8 Menu Line Parameter

Page 142

iCOM Controls Training and Service Manual Service Menu: Electric Heater 2 Settings Maintenance / Wellness Parameters: Page 6 of 8 Menu Line Parame

Page 143

iCOM Control Training and Service Manual Service Menu: Humidifier Settings Maintenance / Wellness Parameters: Page 8 of 8 Menu Line Parameter Def

Page 144

iCOM Controls Training and Service Manual Service Menu: Diagnostics / Service Mode: Page 2 of 5 Menu Line Parameter Range S312 Password - S313 H

Page 145 - NTC (Code S606 and S608)

iCOM Control Training and Service Manual Service Menu: Diagnostics / Service Mode: Page 4 of 5 Menu Line Parameter Range S334 Password - S335 St

Page 146

iCOM Controls Training and Service Manual Service Menu: Set Alarm Parameters S200 series: Page 1 of 6 Menu Line Parameter Default Range S201 Pass

Page 147 - Troubleshooting Checklist

iCOM Control Training and Service Manual Service Menu: Set Alarm Parameters: Page 3 of 6 Menu Line Parameter S223 Password S224 DELAY

Page 148 - User Menu

iCOM Controls Training and Service Manual Service Menu: Set Alarm Parameters: Page 5 of 6 Menu Line Parameter S249 Password S250 DELAY

Page 149

iCOM Control Training and Service Manual untrue type of statement is not used. The consideration now is how to set the input value into a membership

Page 150 - Service Menu

iCOM Control Training and Service Manual Service Menu: Sensor Calibration/ Setup Parameters S600 series: Page 1 of 3 Menu Line Parameter Range S60

Page 151

iCOM Controls Training and Service Manual Service Menu: Sensor Calibration/ Setup Parameters: Page 3 of 3 Menu Line Parameter Default Range S623 P

Page 152

iCOM Control Training and Service Manual Service Menu: System / Network Setup Parameters Series S800: Page 2 of 2, System View Menu Line Function

Page 153

iCOM Controls Training and Service Manual Service Menu: System / Network Setup Parameters Series S800: Page 2 of 2, Unit View Menu Line Function D

Page 154

iCOM Control Training and Service Manual Service Menu: Option Setup Parameters S400 series:: Page 2 of 2 Menu Line Function Default Range S412 Pa

Page 155 - Advanced Menu

iCOM Controls Training and Service Manual Advanced Menu Parameters The Advanced menu displays allows the service technician to set the unit configurat

Page 156

iCOM Control Training and Service Manual Advanced Menu: Factory Settings Parameters A100 series: Page 2 of 6 Advanced Menu: Factory Settings Param

Page 157 - Glossary of Terms

iCOM Controls Training and Service Manual Advanced Menu: Factory Settings Parameters: Page 4 of 6 Advanced Menu: Factory Settings Parameters A100 s

Page 158

iCOM Control Training and Service Manual Advanced Menu: Factory Settings Parameters: Page 6 of 6 Menu Code Parameter Default Range A145 Password

Page 159

iCOM Controls Training and Service Manual Advanced Menu: Factory Access Parameters A200 series: Menu Code Parameter Default Range A201 Password

Page 160

iCOM Controls Training and Service Manual more efficient and precise for most applications, but system performance based on room conditions is not as

Page 161 - Computer and Network Terms

iCOM Control Training and Service Manual Events Notifications Parameters ID Type Description (Large Display) Description (Small Display) 000 Alar

Page 162

iCOM Controls Training and Service Manual Events Notifications Parameters (continued) ID Type Description (Large Display) Description (Small Displ

Page 163

iCOM Control Training and Service Manual Events Notifications Parameters (continued) ID Type Description (Large Display) Description (Small Displa

Page 164 - The industry has

iCOM Controls Training and Service Manual Events Notifications Parameters (continued) ID Type Description (Large Display) Description (Small Displa

Page 165

iCOM Control Training and Service Manual 007 LOSS OF AIRFLOW not enough airflow through the unit. this event can be set to switch off the unit or to d

Page 166 - Network Information

iCOM Controls Training and Service Manual 028 HUM HRS EXCEEDED actual working hours of the fan are higher than the threshold set. Warning no no - 02

Page 167 - 192.168.168.1

iCOM Control Training and Service Manual 048 Unit 7 disconnected " Warning no no - 049 Unit 8 disconnected " Warning no no - 050 Unit 9

Page 168 - How To Use The Schematics

iCOM Controls Training and Service Manual 072 COMP 2 OVERLOAD Compressor 2 stopped because of overload Alarm no yes yes (broken co will remain off

Page 169 - Electrical Schematics

iCOM Control Training and Service Manual 098 DIG SCROLL2 HIGH TEMP Digital Scroll compressor #1 shut off because of high temperature (sensor is inside

Page 170

iCOM Controls Training and Service Manual 114 UNIT CODE MISSING this alarm appears if a totally new board was started the very first time in its life.