www.Fisher.comSupplement to FisherR FIELDVUEt DVC6000 SISDigital Valve Controllers for Safety InstrumentedSystem (SIS) Solutions Instruction ManualPre
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 201110 When the Setup Wizard is complete, you will be prompted to run Auto Travel Calibrat
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 201111 Once Auto Travel Calibration is complete, Partial Stroke Calibration will automatic
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 201112Step 4: Step Response Test Put the DVC6000 SIS Out of Service to run the Step Respon
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 201113 Check the resulting graph to determine if the Step Response test results meets requ
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 201114Step 5: Total Scan Select Spec Sheet and fill in the information under the Valve, Tr
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 201115 Click on Run Diagnostic to start the Total Scan.Figure 24. Total ScanCLICK TO RUN D
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 201116Step 6: Partial Stroke Test Select Partial Stroke > Ramp under the Diagnostics me
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 201117 Verify that the test parameters are correct.Figure 27. Verify Test ParametersTHESE
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 201118 If any Partial Stroke Test data is present in the microprocessor memory, it will be
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 201119 Click on the Signature Analyzer button to analyze friction of the valve. Signature
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 20112Flow Chart Check for proper mounting of theDVC6000 SIS to the actuator Check to ensu
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 201120 Clicking on the Add Overlay button allows you to overlay a graph from a previously
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 201121Step 7: ProtectionIf this is the final set up / configuration before the DVC6000 SIS
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 201122 To disable protection, select Change Protection from the Instrument Setup menu. Fol
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 201123Figure 36. Disable Protection (continued) Set DVC6000 SIS protection to Configuratio
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 201124Related Documents Bulletin 62.1:DVC6000 SIS - Fisher FIELDVUE DVC6000 SIS Digital V
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 20113Step 1: Visual Inspection WARNINGThese guidelines assume that the DVC6000 SIS is prop
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 20114Use ValveLink software to communicate with the DVC6000 SIS. Select Status from the Dia
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 20115Figure 4. Multi‐Drop Control ModeDIP SWITCH SET TO MULTIEND MONITORINGStep 3: Setup Wi
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 20116Figure 6. Set the Instrument Out of Service After the DVC6000 SIS has been set out of
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 20117 Select the Actuator Make, Model, and Size. Check the box if a Volume Booster / Quick
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 20118 Select the Partial Stroke Test Starting Point according to the application. Remove c
Instruction Manual SupplementD103285X012DVC6000 SISJanuary 20119 Select the appropriate Tuning Set. Refer to the Detailed Setup section of the DVC600