Specifications Overview1
1Overview
Retail Solutions specs a modular refrigerant leak
detection sensor (MRLDS) that continuously monitors for
low levels of refrigerants most commonly used in com-
mercial refrigeration systems.
The MRLDS communicates with the E2 controller via
direct connect MODBUS, a Gateway board connected to
the RS485 I/O Network, or via the analog input on a Mul-
tiFlex board.
1.1 Specifications
*De-icer: for environments below 32°F to keep ice from
forming on the surface of enclosure.
1.2 MRLDS Models
1.3 Powering The MRLDS
The MRLDS unit requires a separate UL Listed/CSA
Certified 24VAC Class 2 transformer power supply. One
24VAC, 10VA Class 2 transformer is sufficient for up to
three (3) MRLDS units.
Retail Solutions supplies several sizes of transformers
for powering multiple MRLDS units (three or more). Note
that polarity must be maintained when connecting more
than one MRLDS to a single transformer.
Power Require-
ments
24 VAC, ±20%, 50/60 Hz, Class 2
Wiring
14 AWG max, Class 2 copper wir-
ing
Power Consump-
tion
Less than 2.7 watts
Output Options
1-5V, 10 K Ohm load
RS485 Modbus RTU
Operating Temp.
32 to 149°F (-22 to 149°F with
de-icer*)
0 to 65°C (-30 to 65°C with
de-icer*)
Humidity
0 to 99% non-condensing
Size
4.5” x 3.5” x 1.6”
Weight
.35 lbs. (160 g)
Pollution Degree
2
Installation Cate-
gory
II
Range
0 to 1000 PPM
Minimum Detec-
tion
25 PPM
Pressure
Operating 10.2 to 15.7 PSIA
Repeatability
±10 PPM at 50 PPM
Linearity
See Table 6-2, “- Linearity Settings
for Supported Refrigerants,” on
page 18
Warm-up Time
30 minutes
Table 1-1 - MRLDS Unit Specifications
Figure 1-1 - Sensor Base Opening With Screw Terminals
Part Number Description
809-1000 Voltage Out w/o de-icer*
809-1001 Voltage Out with de-icer*
809-1010 Modbus w/o de-icer*
809-1011 Modbus with de-icer*
Table 1-2
- Available MRLDS Models
Part Number Transformer
Description
Number of
MRLDS Units
Powered
640-0039 24VAC, 10VA
Class 2
Up to 3
Table 1-3
- MRLDS Transformer Specifications
WARNING: The MRLDS unit must be always
be powered by either a suitable UL 60950/CSA
Certified power supply that is isolated from line
voltage by double insulation, or an appropriately rated
UL Listed/CSA Class 2 transformer. Failure to follow
the above can result in serious personal injury or death.