E2 Setup of MRLDS E2 MODBUS Direct Support for MRLDS5
4. This screen will have a “Connection” field
for all COM ports on the E2. Highlight the
COM port connection field that will be used,
and press
- LOOK UP. From the list
of network types, select MODBUS.
5. Four fields will become visible underneath
the COM port connection field, which pertain
to the way the device communicates:
Baud - Default setting is 19200. Leave this
field at the default value.
Data Size - Leave this field at the default
value (8).
Parity - Leave this field at the default value
(None).
Stop Bits - MRLDS value is two (2).
6. Press
to save changes and exit.
3.2.2 Add and Connect MRLDS
To enable communications between E2 and the
MRLDS, the devices must be added and addressed in E2.
1. Log in to the E2 with Level 4 access.
2. Press
 - Connected I/O
Boards and Controllers.
3. On the ECT tab screen enter the number of
MRLDS Panels in the MRLDS number field.
4. Press
to return to the Network Setup
menu, then select
- Network Summary
(Figure 3-6).
5. Locate the MRLDS you added to the network
list (press
and to scroll through the
list) and highlight with the cursor. Press
for Setup.
Each MRLDS is assigned a MODBUS address au-
tomatically when it is created.
6. Locate the MRLDS you set up, and look at
each device’s status in the Status field. You
Figure 3-4
- Serial Communications Manager Screen
Figure 3-5 - Connected I/O Screen
Figure 3-6 - Network Summary Screen