Emerson 80-150kW White Paper Page 5

  • Download
  • Add to my manuals
  • Print
  • Page
    / 12
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 4
Liebert
®
iCOM Controls: The Industry’s
Most Advanced Control System
The Liebert DSE™ is managed by the latest Liebert
iCOM intelligent controls, which enable the system to
continuously adapt to the data center IT load and outdoor
conditions to take full advantage of economization while
providing consistent cooling to IT equipment. The controls
monitor all cooling system components as well as inlet rack
temperatures throughout the data center.
Monitoring inlet temperatures provides two primary
benets: rst, it enables the Liebert DSE system to adjust
cooling capacity to the exact amount of cooling needed.
Second, the inlet rack temperature may be reported back
to a building management system and recorded to ensure
service level agreements are met.
The Liebert iCOM controls scale the operation of the CRAC
to variably modulate the air volume and compressor
capacity to precisely match the data center’s IT load,
enabling the CRAC unit to deliver the right amount of air at
the right temperature. Liebert iCOM also monitors the load
and outdoor conditions to control the outdoor Liebert MC™
micro-channel condenser, and during cooler temperatures,
automatically activates the Liebert EconoPhase pumped
refrigerant economizer to provide economization when
conditions are optimal to do so.
The system’s integrated Liebert iCOM controls also monitor
several parameters within each sub-system and coordinate
operation to provide efcient and reliable cooling. The
Liebert iCOM control system provides hassle-free operation
by automatically transferring between mechanical cooling
and economizer operation modes. Built-in diagnostics
ensure that system reliability is maintained, and information
about system operation is reported.
Comparing Economizer Designs and
Efficiency Implications
Traditional direct expansion systems packaged with water-
side economizers utilize a direct expansion cooling coil
overlaid by a closed loop of water/glycol refrigerant solution.
When ambient temperatures are low enough, the system’s
pump moves the water/glycol solution from an outdoor uid
cooler (or drycooler) to the system’s indoor economizer coil.
While this type of system can provide economization and
reduce compressor operation, its efciency is hampered by
the energy required for the pump to move a highly viscous
water/glycol solution. In addition, the glycol solution itself—
especially a propylene glycol solution—signicantly reduces
heat transfer of the economizer coil, resulting in very low
ambient temperatures required to provide full cooling.
The Liebert EconoPhase requires much less power to pump
refrigerant than alternative systems that pump glycol.
The Liebert EconoPhase maintains full cooling capacity by
taking advantage of the two-phase properties of refrigerant.
Alternative glycol-based economizers can experience
capacity reduction as much as 40 percent compared to
full-DX operation resulting in a need to oversize the
economizer to reach system rated capacity. Water-side
economizers require extra fan power year-round, due to
the additional heat exchange that overlays the DX coil. The
Liebert DSE system requires no additional economizer coils,
keeping air-side pressure drop lower, resulting in lower
indoor fan energy consumption
1
.
Another option is to use chilled water air handlers
(CRAHs) in conjunction with a chiller plant and an air-side
economizer. In this conguration, the chiller plant produces
cold water during warmer times of the year, and outdoor
air is brought into the data center when conditions are
right. However, some end-users do not wish to change
1
According to ASHRAE 90.1-2010, data centers are now required to meet mandatory requirements for minimum SCOP (full-load,
design day) to achieve a satisfactory efciency rating per ASHRAE rating Standard 127. The ASHRAE 90.1 requirements also mandate
the utilization of economizers in many regions of the United States. This minimum efciency target for direct expansion cooling systems
ranges from 1.8 to 2.6, depending on the cooling capacity, condensing type, and airow conguration.
5
Page view 4
1 2 3 4 5 6 7 8 9 10 11 12

Comments to this Manuals

No comments