Regardless of the system used, an intelligent control system
that evaluates room load, room temperature (or supply air
temperature) and outdoor temperature must be employed
to determine the most optimal operation of system.
When considering total cost of ownership, the Liebert
®
DSE™ with Liebert EconoPhase™ system also compares
very favorably to alternative cooling systems. In order to
compare systems, a complete picture of system costs must
be known and compared. As shown in Figure 8, the Liebert
DSE can deliver a payback in less than three years compared
to traditional air-cooled DX systems, but without the
hassles and risks of other types of economizer systems.
Conclusion
As this brief has demonstrated, the Liebert DSE cooling
system from Emerson Network Power represents the
industry’s most exible, reliable and efcient DX solution.
The Liebert DSE achieves industry-leading efciency by
offering a modular, end-to-end cooling infrastructure,
complete with a high-efciency indoor CRAC unit, a
hassle-free pumped-refrigerant economizer, micro-channel
outdoor condensers with variable-speed fan technology
and a comprehensive data center intelligence and
management system built-in.
Collectively, these components make up a cooling
infrastructure capable of delivering the lowest possible
total cost of ownership and the highest levels of reliability
compared to competitive solutions – all backed by the
largest and most experienced sales and support team in the
data center industry.
Traditional
Air-Cooled DX
Chilled Water Chilled Water
Liebert DSE with
EconoPhase
Economizer None None Air Economizer Pumped Refrigerant
Energy Cost $416,000 $276,000 $251,000 $231,000
Water Cost $0 $32,000 $21,000 $0
Total Utility $416,000 $308,000 $272,000 $231,000
Annual Cooling PUE 1.32 1.21 1.19 1.16
Capital Cost $1,900,000
$2,200,000
$3,100,000 $2,500,000
Payback Base 4.9 years 5.6 years 2.7 years
15-Year PV $5,200,000 $4,900,000 $5,600,000 $4,100,000
Figure 8: Analysis of total cost of ownership across cooling system options, taking into consideration capital expenditure and operating
expenditure for a data center with a 1,500 kW load, $0.10/kWh utility cost and 40 degree dew point limit, based on Columbus, Ohio
weather data. The chilled water systems assume an entering water temperature of 50°F, with a water temperature difference of 12°F.
11