System Maintenance
28
5.2 Special Procedures
5.2.1 Drycooler Cleaning
Keeping the outdoor drycooler coils clean is an important factor in maintaining peak efficiency,
reliability and long life of the equipment. It is much easier to keep up on frequent cleanings rather
than wait until heavy build up has occurred which may create head pressure problems with the
evaporator units.
When to Clean
Normal conditions typically dictate cleaning twice a year, spring and fall. On-site or area conditions
such as cottonwood trees, construction, etc., can increase cleaning frequency. On your standard
bimonthly or quarterly preventive maintenance schedule, a visual inspection of the coil is
recommended to monitor conditions.
What to Use
The best overall condenser coil cleaner to use is plain water. If the coil has been maintained and
cleaned at regular intervals, water is sufficient to remove dirt and debris from the fins. Heavy buildup
on the exterior of the fins can be removed with a brush. Water pressure from a garden hose and
sprayer usually works well. If a pressure washer is used, make sure the equipment is set to a lower
pressure setting and that the nozzle is set to the fan spray, not stream. Otherwise, damage to the fins
could result. If a cleaner is required, Emerson
®
recommends using a non-acidic type cleaner. Acid-
type cleaners can be aggressive to the coil fins as well as surrounding areas. Many sites do not allow
the use of acidic cleaners for environmental reasons.
How to Clean
The best way to clean coils is from the inside out. This requires removing the coil guards or grilles (if
provided), the fan guards and blades to access the coil surface. The sprayer can then be worked across
the coil pushing the dirt and debris out. Although this does extend the time involved, the results are
well worth it. This method should be used at least once a year. Spraying the coil from the outside
repeatedly can push a majority of the dirt to the inner section of the fins and continue to restrict air
flow. Keep in mind you may not have the luxury of shutting the unit(s) down for an extended time. A
scheduled shutdown with the operator may be in order. If using a cleaner along with the spraying
process, follow recommended manufacturer instructions and be sure to rinse the coil thoroughly. Any
residue left on the coil can act as a magnet to dirt.