Instruction Manual
D102005X012
846 Transducer
March 2015
9
ATEX
Special Conditions for Safe Use
Intrinsically Safe
This equipment is intrinsically safe and can be used in potentially explosive atmospheres.
The apparatus must be only connected to a certified associated intrinsically safe equipment and this combination
must be compatible as regards intrinsic safety rules.
The electrical parameters of certified equipment which can be connected to the sensor must not exceed one of these
following values:
U
0
≤ 30 V
I
0
≤ 100 mA
P
0
≤ 1.0 W
Ambient temperature: -40_C to +80_C
Flameproof
Refer to page 10.
Type n
No special conditions for safe use.
Refer to table 2-3 for additional approval information.
Table 2-3. Hazardous Area Classifications—ATEX
Certificate Certification Obtained Entity Rating Temperature Code
ATEX
Intrinsically Safe
II 1 GD
Gas
Ex ia IIC T4,T5 Ga
Dust
Ex ia IIIC IP66 Da T90_C (Tamb ≤ 80_C)
Ex ia IIIC IP66 Da T50_C (Tamb ≤ 40_C)
Ui = 30 VDC
Ii = 100 mA
Pi = 1.0 W
Ci = 8 nF
Li = 20 mH
T4 (Tamb ≤ 80_C)
T5 (Tamb ≤ 40_C)
Flameproof
II 2 G
Gas
Ex d IIB T5/T6 Gb
- - -
T5 (Tamb ≤ 80_C)
T6 (Tamb ≤ 65_C)
Type n
II 3 GD
Gas
Ex nA IIC T5/T6 Gc
Dust
Ex tc IIIC T88_C T
500
Dc IP66
Ex tc IIIC T77_C T
500
Dc IP66
- - -
T5 (Tamb ≤ 85_C)
T6 (Tamb ≤ 74_C)
Comments to this Manuals