Emerson CS400 Datasheet Page 14

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 13
Bulletin 71.1:CS400
14
Table 10. Type CS400 Relief Table, 7 in. w.c. / 17 mbar Setpoint, Internal Registration
ORIfICE SIzE REGULATOR SET PRESSURE
MAXIMUM INLET PRESSURE TO kEEP OUTLET PRESSURE AT/OR bELOW
(1)
 
In. mm In. w.c.     
3/16 4.8
7 17
46 3.2 100 6.9
1/4 6.4 23 1.6 54 3.7
5/16 7.9 15 1.0 31 2.1
3/8 9.5 9 0.62 20 1.4
1. Relief values obtained by blocking regulator open per orice.
0.5 /
34
1 /
69
1.5 /
103
2 /
138
2.5 /
172
3 /
207
0


Figure 10. Type CS400IR Relief Curves (Blocked per Orice Size) at 7 in. w.c. / 17 mbar Set Pressure
3/16 in. /
4.8 mm
ORIfICE
1/4 in. /
6.4 mm
ORIfICE
5/16 in. /
7.9 mm
ORIfICE
1/2 in. /
13 mm
ORIfICE
5/8 in. /
16 mm
ORIfICE
3/8 in. /
9.5 mm
ORIfICE
3/4 in. /
19 mm
ORIfICE
100 /
6.9
50 /
3.4
10 /
0.69
20 /
1.4
30 /
2.1
40 /
2.8
60 /
4.1
70 /
4.8
80 /
5.5
90 /
6.2
110 /
7.6
120 /
8.3