AC PowerFor Business-Critical Continuity™Liebert Series 610™ UPSInstallation Manual - 1000kVA, 60Hz, Three Phase Single-Module
Inspections63.0 INSPECTIONS3.1 External Inspections1. While the UPS system is still on the truck, inspect the equipment and shipping container(s) for
Equipment Location74.0 EQUIPMENT LOCATION1. Handle cabinet(s) in accordance with the safety precautions in this manual, especially in these sections:•
Battery Installation85.0 BATTERY INSTALLATION5.1 Battery Safety PrecautionsServicing of batteries should be performed or supervised by personnel knowl
Battery Installation95.2 Battery Safety Precautions in French Per CSA RequirementsInstructions Importantes Concernant La SécuritéConserver Ces Instruc
Battery Installation105.3 Battery CabinetsOptional battery cabinets are available from Liebert and other qualified vendors. Consult your sub-mittal pa
Battery Installation115.4 Open-Rack BatteriesWhen batteries other than Liebert battery cabinets are used, a remote battery disconnect switch with over
Configuring Your Neutral and Ground Connections126.0 CONFIGURING YOUR NEUTRAL AND GROUND CONNECTIONSImproper grounding is the largest single cause of
Configuring Your Neutral and Ground Connections136.1 Preferred Grounding Configuration, Wye-Connected ServiceOne of the most common configurations of
Configuring Your Neutral and Ground Connections146.2 Alternate Grounding Configuration, Wye-Connected ServiceThis configuration must NOT be used when
Configuring Your Neutral and Ground Connections156.3 Preferred Grounding Configuration With Isolated BypassAnother configuration in this power range i
BATTERY CABINET PRECAUTIONSThe following warning applies to all battery cabinets supplied with UPS systems. Additional warnings and cautions
Configuring Your Neutral and Ground Connections166.4 Alternate Grounding Configuration, Non-IsolatedA few applications in this power range have 208 VA
Configuring Your Neutral and Ground Connections176.5 Grounding Configuration, Corner-Grounded Delta or Impedance-Grounded WyeAs previously mentioned,
Configuring Your Neutral and Ground Connections186.6 Preferred Grounding Configuration, Battery SystemsOpen-rack battery systems, depending on local c
Wiring Considerations197.0 WIRING CONSIDERATIONSRefer to Appendix A and drawings in 10.0 - Installation Drawings. Determine AC currents for your syste
Wiring Considerations207.1 Power Wiring1. Power wiring—rectifier input, bypass input, UPS output and battery cables—must be run in individual, separat
Wiring Considerations21Figure 8 Power single-line diagrams** These configurations are for illustrative purposes only. They represent only a sample of
Wiring Considerations22Table 1 Abbreviations for circuit breakersBFB Bypass Feeder BreakerBIB Bypass Input BreakerMBB Maintenance Bypass BreakerMBD Mo
Wiring Considerations237.2 Control WiringControl wiring must be flexible stranded, tinned copper and run in individual separate steel conduits. Contro
Wiring Connections248.0 WIRING CONNECTIONS !WARNINGVerify that all incoming high and low voltage power circuits are de-energized and locked out before
Wiring Connections258.1 Specific ConnectionsRefer to the drawings in this manual and any other drawings provided by Liebert for this installation.Make
iTABLE OF CONTENTSBATTERY CABINET PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . INSIDE FRONT COVERCONTACTING LIEBERT F
Wiring Inspection269.0 WIRING INSPECTION1. Verify all power connections are tightened per the torque specifications in Table 3.2. Verify all control w
Wiring Inspection27Table 4 Field-supplied lugsOne-Hole LugsT & B1 Lug Style Wire Size Bolt Size (in.) Tongue Width (in.) T & B1 P/N Liebert P/
Wiring Inspection28Table 5 Table 310-16, National Electrical Code (Reprint)Allowable Ampacities of Insulated Conductors Rated 0-2000 Volts, 60° to 90°
Installation Drawings2910.0 INSTALLATION DRAWINGSFigure 9 Outline drawing, 1000kVA, front-access Single-Module UPS, 480V and 600V88-791685-14Rev. 03
Installation Drawings30Figure 10 Bussing details, 1000kVA, front-access Single-Module UPS, 480V and 600V88-791685-34Rev. 03
Installation Drawings31Figure 11 Base mounting details, 1000kVA, Single- and Multi-Module rectifier and inverter sections88-791613-08Rev. 03
Installation Drawings32Figure 12 Base mounting details, 1000kVA, Single- and Multi-Module control section88-791613-09Rev. 04
Installation Drawings33Figure 13 Shipping split detail, 1000kVA, Single- and Multi-Module UPS88-791612-09Rev. 04
Installation Drawings34Figure 14 Control connection location diagram, Single-Module system, 1000kVA96-791619-76Rev. 03
Installation Drawings35Figure 15 Wiring diagrams, Single-Module System, interconnect diagram96-791619-01ARev. 02
iiFIGURESFigure 1 Preferred grounding configuration, wye-connected service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Figure 2 Alt
Installation Drawings36Figure 16 Control wire list, Single-Module System, external interconnection, Part 196-791619-05ARev. 02
Installation Drawings37Figure 17 Control wire list, Single-Module System, external interconnection, Part 296-791619-06Rev. 03
Installation Drawings38Figure 18 Control wire list, Single-Module System, external interconnection, optional internal modem96-791619-14Rev. 03
Installation Drawings39Figure 19 Control wire list, Single- and Multi-Module System, external interconnection, optional battery temperature sensor96-7
Installation Drawings40Figure 20 Control wire list, Single-Module System, external interconnection, optional customer alarm interface96-791619-11Rev.
Installation Drawings41Figure 21 Outline drawing, single-breaker module battery disconnect, 1400AT/1600AT/2000AT/2500AT, 600VDC circuit breaker88-7976
Installation Drawings42Figure 22 Outline drawing, remote status panel, surface mount88-791617-01Rev. 05
Site Planning Data, 1000kVA, Single-Module Systems43APPENDIX A-SITE PLANNING DATA, 1000KVA, SINGLE-MODULE SYSTEMSNotes for Tables 6 and 7 1. Nominal r
Site Planning Data, 1000kVA, Single-Module Systems44 Table 6 Site planning data—600V inputUPSRatingAC OutputVoltage OptionsBypass ACInput CurrentRecti
Site Planning Data, 1000kVA, Single-Module Systems45NOTES
1IMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONSThis manual contains important instructions that should be followed during installation of your S
Site Planning Data, 1000kVA, Single-Module Systems46
EmersonNetworkPower.comEnsuring The High Availability0f Mission-Critical Data And Applications.Emerson Network Power, the global leader in enabling bu
2!CAUTIONThis unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules and EN550022. These limits pr
Installation Considerations31.0 INSTALLATION CONSIDERATIONSInstall your Series 610 UPS in accordance with the submittal drawing package and the follow
Installation Considerations410. A breaker coordination study should be performed to ensure proper handling of fault currents.NOTEThe instantaneous tri
Unloading and Handling52.0 UNLOADING AND HANDLINGUPS modules are shipped in split cabinets to allow ease of handling. Because the weight distribution