Emerson E2 Operator's Manual Page 42

  • Download
  • Add to my manuals
  • Print
  • Page
    / 71
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 41
42
Flashing d
Loss of Communication Mode
(continued)
Communication Troubleshooting
DC Voltage 2.3v - 2.6v (all devices must be connected to the communications
network)
Voltage between 485+ and 485- is typically less than 0.3vdc.
An open wire, poor connection or misplaced jumper will affect voltage.
Communication Board Troubleshooting
The communication board is a sacrificial element to protect the main board from
damage due to voltage spikes.
DC Voltage output 2.3 - 2.6v
0 volts brown to red or black to red indicate a damaged communication board.
Replace communication board (see parts list).
2.3 to 2.6 VDC
Touch
points to
measure
voltage
AE8-1337 R1