Service Menu Parameters
85
Digital Scroll 2 NTC—This parameter adjusts the digital scroll 1 NTC reading from the actual sen-
sor to compensate for any error or drift of the sensor.
Calibrated Digital Scroll 2 NTC—This parameter shows the adjusted Digital Scroll 1 NTC sensor
value. This value is the actual sensor reading (+ or -) the offset “Digital Scroll 1 NTC”.
Figure 76 Sensor calibration / setup parameters - Page 2
Optional Sensor A, B & C—This parameter adjusts the reading from the actual sensor to compen-
sate for any error of the sensor or to match other sensors in the room.
Calibrated Optional Sensor A, B & C—This parameter shows the adjusted value of the sensor.
This value is the actual sensor reading (+ or -) the offset.
Optional Sensor B &C Type—This parameter currently only supports the “TH” Temperature /
Humidity sensor type.