5-3
Rosemount 3051S
Figure 5-2. Problems with
communications flowchart
COMMUNICATIONS ESTABLISHED BUT HAVE
“BLOCK_ERR” OR AN “ALARM” CONDITION.
See "PlantWeb Alerts" on page 5-10
Read the following parameters in the
Resource Block to determine the
recommended action.
BLOCK_ERR (see Table 5-2)
SUMMARY_STATUS (see Table 5-3)
DETAILED_STATUS (see Table 5-4)
Problem Identified?
Yes
No
Perform Recommended
Action, see Table 5-4.
For more detailed
information
Perform the following steps in the Sensor
Transducer Block to determine the
recommended action.
BLOCK_ERR (see Table 5-5)
XD_ERR (see Table 5-6)
DETAILED_STATUS (see Table 5-7)
RECOMMENDED_ACTION (see Table 5-7)
If error condition does not exist
in the Resource Block then it is a
configuration problem, see “AI
BLOCK_ERR Conditions.” in
Table 5-8
Problem Identified?
Yes
No
If the problem persists
contact your local
Rosemount representative.
Problem Identified?
Perform Recommended
Action, see Table 5-7.
Yes
No
Perform Recommended
Action, see Table 5-9.
Yes
No
Perform Recommended
Action, see Table 2-1.
Problem Identified?