Smart Wireless Gateway
August 2014
1410 Gateway Product Specifications
Functional specifications
Input voltage
10.5-30 VDC
Current draw
Operating current draw is based on 3.6 Watts power
consumption.
Environmental
Operating temperature range:
-40 to 167 °F (-40 to 75 °C)
Operating humidity range:
0-100% relative humidity
EMC performance
Complies with EN61326-1:2006.
Antenna options
See 781 specifications.
Physical specifications
Weight
0.70 lb. (0,318 kg)
Material of construction
Housing
Polycarbonate
Rail mount
Top hat rail EN 50022 35 mm X 7.5 mm and 35 mm x 15 mm
Communication specifications
Isolated RS-485
2-wire communication link for Modbus RTU multidrop
connections
Baud rate: 57600, 38400, 19200, or 9600
Protocol: Modbus RTU
Wiring: Single twisted shielded pair, 18 AWG. Wiring distance is
approximately 4000 ft. (1,524 m)
Ethernet
10/100base-TX Ethernet communication port
Protocols: Modbus TCP, OPC, EtherNet/IP, HART-IP, https (for
Web Interface)
Wiring: Cat5E shielded cable. Wiring distance 328 ft. (100 m).
Modbus
Supports Modbus RTU and Modbus TCP with 32-bit floating
point values, integers, and scaled integers.
Modbus Registers are user-specified.
OPC
OPC server supports OPC DA v2, v3
EtherNet/IP
Supports EtherNet/IP protocol with 32 bit Floating Point values
and Integers. EtherNet/IP Assembly Input-Output instances are
user configurable. EtherNet/IP specifications are managed and
distributed by ODVA. For details on capabilities please see the
Smart Wireless Gateway to Allen Bradley Integration Manual
(document number 00809-0500-4420) on rosemount.com.
12 24
30
125
250
Voltage (VDC)
Current (mA)