Operation
The Motor Amps Load Limit protects the com-
pressor from overloading by decreasing the
compressor capacity if the motor amperage is
at the Maximum Amps setpoint, or preventing
an increase in capacity if the motor amperage is
above the Full Load Amps setpoint. (See Com-
pact Logix PLC manual, p/n 35391CL.)
3. Oil Separator Heater
The oil separator heater keeps the oil in the
separator from becoming too viscous and helps
keep gas from condensing in the receiver section
of the separator.
The heater is turned on only when the compres-
sor is off. The separator heater is supplied with
an integral temperature control.
B. Safety Setpoints
A detailed explanation of all safety setpoints can
be found in the Compact Logix PLC manual, p/n
35391CL.
1. Oil Pressure
Low oil pressure differential stops the compres-
sor unit when there is an insufficient difference
in pressure between the oil manifold and suc-
tion.
2. Discharge Pressure
High discharge pressure cutout stops the com-
pressor unit, when the discharge pressure in the
oil separator exceeds the setpoint.
3. Suction Pressure
Low suction pressure cutout stops the
compressor unit when the suction pressure
drops below the setpoint.
4. Oil Filter Differential
High oil filter differential cutout stops
the compressor unit when the difference
between the outlet and inlet of the filter
exceeds the setpoint.
5. Oil Temperature
The oil temperature cutout stops the com-
pressor unit when the oil temperature is too
high or too low.
6. Discharge Temperature
The high discharge temperature cutout
stops the compressor unit when the dis-
charge temperature exceeds the setpoint.
INITIAL START-UP
A. Setting of Controls
Refer to the Compact Logix PLC manual (p/n
35391CL) for a list of initial settings.
B. Valve Settings
1. The suction line uses separate stop and check
valves. Ensure the suction stop valve is open
prior to starting.
2. The ¼” suction equalization valve should be
closed during operation. The valve enables the
unit to slowly equalize to low side pressure dur-
ing off periods. This valve must be adjusted to
minimize oil loss when compressor stops.
3. The discharge line uses separate stop and check
valves. Ensure the discharge valve is open prior
to starting.
4. Manually open the oil isolating valve at the oil
separator outlet connection.
5. Open the isolating valve(s) before and after the
oil filter housings.