Emerson Type 1190 Low-Pressure Gas Blanketing Regulator Datasheet

Browse online or download Datasheet for Unknown Emerson Type 1190 Low-Pressure Gas Blanketing Regulator. Emerson Type 1190 Low-Pressure Gas Blanketing Regulator Data Sheet User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 12
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Bulletin 74.1:1190
April 2012
D101962X012
www.sherregulators.com
Type 1190 Low-Pressure Gas Blanketing Regulator
Introduction
The Type 1190 low-pressure gas blanketing regulator
is used for extremely accurate pressure control on
very low-pressure blanketing systems. The regulator
helps to control emissions and provides protection
against any contamination from atmospheric conditions
by providing a ushing action. The Type 1190 gas
blanketing regulator maintains a positive vessel
pressure thereby reducing the possibility of vessel wall
collapse during pump-out operations.
A Type 1190 low-pressure gas blanketing regulator
reduces a high-pressure gas, such as Nitrogen, to
maintain a protective environment above any liquid
stored in a tank or vessel while the liquid is being
pumped out. Also, when the vessel cools suddenly
causing the vapors inside the vessel to condense,
the gas blanketing regulator replaces the condensed
vapors with the blanketing gas to prevent the internal
vessel pressure from decreasing. In both cases a
slight positive vessel pressure prevents outside air,
moisture, and other contaminants from entering the
vessel and the possible collapse of the vessel walls.
Features
Quick-Change Trim Package—Tested trim
packages can be made up and stocked ahead of
time for fast replacement.
In-Service Travel Inspection—Standard
indicator assembly with protective cover permits
periodic inspection of plug travel without removing
regulators from service.
Easy In-Line Maintenance—Top-entry design
reduces maintenance time and manpower
requirements; trim parts can be inspected,
cleaned, and replaced without removing the main
valve body from the pipeline.
Factory-Piped Pilot Supply—Supply pressure to
pilot is supplied from inlet side of the main valve
body through tubing furnished with the regulator.
Figure 1. Type 1190 Low-Pressure Gas Blanketing Regulator
W7428
Page view 0
1 2 3 4 5 6 ... 11 12

Summary of Contents

Page 1 - Bulletin 74.1:1190

Bulletin 74.1:1190April 2012 D101962X012www.sherregulators.comType 1190 Low-Pressure Gas Blanketing RegulatorIntroductionThe Type 1190 low-pressure g

Page 2

Bulletin 74.1:119010Ordering GuideConstruction (Select One)  Standard  NACEType EGR Main ValveMain Valve Body Size (Select One)  NPS 1 / DN 25

Page 3

Bulletin 74.1:119011Ordering Guide (continued)Type 1098 ActuatorLower Diaphragm Case Material (Select One)  Steel***  Stainless steel (NACE)**Bo

Page 4

Bulletin 74.1:1190©Emerson Process Management Regulator Technologies, Inc., 1993, 2012; All Rights ReservedThe Emerson logo is a trademark and service

Page 5

Bulletin 74.1:11902SpecicationsBody Sizes(1) See Table 1Maximum Main Valve Inlet Pressures(2) 400 psig / 27.6 barMaximum Operating Inlet Pressures(

Page 6

Bulletin 74.1:11903Specications (continued) Type Y191A Pilot Body, Spring Case, and Diaphragm Casing: Ductile iron (standard) or Stainless stee

Page 7

Bulletin 74.1:11904Principle of OperationThe Type 1190 gas blanketing regulator reduces a high-pressure inert gas to maintain a positive low-pressure

Page 8

Bulletin 74.1:11905When downstream demand has been satised, outlet pressure tends to increase slightly, acting on the pilot and main valve diaphragms

Page 9

Bulletin 74.1:11906Table 5. Maximum and Minimum Differential Pressures for Main Valve Spring SelectionBODY SIZESMAIN VALVE SPRING PART NUMBER SPRING

Page 10

Bulletin 74.1:11907Table 7. Gas Flow Required for Thermal Heating (Outbreathing) or Cooling (Inbreathing) per American Petroleum Institute Standar

Page 11

Bulletin 74.1:11908Table 9. Supply Pressure(1) Settings Required for the Type 95H RegulatorBODY SIZESTYPE EGR SPRING COLORSUPPLY PRESSUREType Y191A

Page 12

Bulletin 74.1:11909MAIN VALVE BODY SIZESDIMENSIONSAD G Z A/RNPTCL125 FF Cast Iron, or CL150 RF Steel, or Stainless SteelCL250 FF Cast Iron, or CL300

Comments to this Manuals

No comments