Fisherr 4195KA, KB, KC, and KS Gauge Pressure
Controllers
Contents
1. Introduction
Scope of Manual 4.............................
Description 4.................................
Specifications 4...............................
Educational Services 4.........................
2. Installation
Controller Mounting Orientation 9...............
Pipestand Mounting 9.........................
Panel Mounting 10............................
Wall Mounting 11.............................
Actuator Mounting 11.........................
Pressure Connections 12.......................
Process Pressure Connection 12..............
Supply Pressure Connection 12..............
Remote Set Point (suffix letter M)
Pressure Connection 13..................
External Feedback Pressure Connection
(4195KB Controllers Only) 13.............
Vent 14......................................
3. 4195KA Proportional‐Only Controllers
Adjustments for 4195KA Controllers 15...........
Manual Set Point Adjustment 15.............
Remote Set Point (suffix letter M)
Adjustment 16..........................
Proportional Band Adjustment (PB ADJ) 16.....
Changing Controller Action 16...............
Switching The Auto/Manual Station
(suffix letter E) 17.......................
Prestartup Checks for 4195KA Controllers 17......
Startup for 4195KA Controllers 18...............
Calibration of 4195KA Controllers 18.............
General Calibration Instructions 19...........
Process Indicator Zero and Span Calibration 19.
Remote Set Point (suffix letter M)
Zero and Span Calibration 21..............
Flapper Alignment 22......................
Principle of Operation for 4195KA Controllers 23...
Overall Operation 23.......................
Remote Set Point (suffix letter M)
Operation 24...........................
Auto/Manual Station (suffix letter E)
Operation 24...........................
4. 4195KB Proportional‐Plus‐Reset
Controllers and 4195KC
Proportional‐Plus‐Reset‐Plus‐Rate Controllers
Adjustments for 4195KB and KC Controllers 25.....
Manual Set Point Adjustment 25.............
Remote Set Point (suffix letter M)
Adjustment 26..........................
Proportional Band Adjustment (PB ADJ) 26.....
Changing Controller Action 26...............
Reset Adjustment 27.......................
Rate Adjustment 27........................
Anti‐Reset Windup (suffix letter F)
Adjustment 27..........................
Switching the Auto/Manual Station
(suffix letter E) 27.......................
Prestartup Checks for 4195KB and KC
Controllers 28..............................
Startup for 4195KB and KC Controllers 28.........
Calibration of 4195KB and KC Controllers 30.......
General Calibration Instructions 30...........
Process Indicator Zero and Span
Calibration 30..........................
Remote Set Point (suffix letter M)
Zero and Span Calibration 32..............
Flapper Alignment 33......................
Anti‐Reset Windup (suffix letter F)
Differential Relief Valve Calibration 35......
Principle of Operation for 4195KB and KC
Controllers 36..............................
Overall Operation 36.......................
Anti‐Reset Windup (suffix letter F)
Operation 39...........................
Remote Set Point (suffix letter M)
Operation 39...........................
Auto/Manual Station (suffix letter E)
Operation 40...........................
External Feedback Operation 41..............
5. 4195KS Differential Gap Controllers
Operating Information 42......................
Adjustments for 4195KS Differential Gap
Controllers 43..............................
Manual Set Point 43........................
Remote Set Point (Option M) 43.............
Proportional Band (Differential Gap) 43.......
Changing Controller Action 43...............
Instruction Manual
D200160X012
4195K Controllers
December 2012
Page view 0
1 2 3 4 5 6 ... 123 124

Summary of Contents

Page 1 - Controllers

www.Fisher.comFisherr 4195KA, KB, KC, and KS Gauge PressureControllersContents1. IntroductionScope of Manual 4...Description

Page 2 - Contents (continued)

Instruction ManualD200160X0124195K ControllersDecember 201210Figure 2‐2. Pipestand Mounting49A3196‐AA6732HEX HEADCAP SCREW(KEY 66)LOCKWASHER(KEY 67)HE

Page 3

Instruction ManualD200160X0124195K ControllersDecember 20121003. Adjust the remote set point pressure to 100 percent of the remote set point input ra

Page 4 - Section 1 Introduction

Instruction ManualD200160X0124195K ControllersDecember 2012101CAUTIONIn the next step, take care to tighten the two screws (keys 314 and 315) evenly.

Page 5

Instruction ManualD200160X0124195K ControllersDecember 20121027. Remove the O‐rings (keys 292, 293, and 294), switch body springs (key 295), and ball

Page 6

Instruction ManualD200160X0124195K ControllersDecember 2012103Refer to figure 7‐7 for key number locations.Disassembly1. Remove the auto/manual stati

Page 7

Instruction ManualD200160X0124195K ControllersDecember 2012104Refer to figure 7‐7 for key number location.1. Remove the controller assembly from the

Page 8

Instruction ManualD200160X0124195K ControllersDecember 2012105Section 7 PartsParts OrderingWhenever corresponding with your Emerson Process Management

Page 9 - Section 2 Installation

Instruction ManualD200160X0124195K ControllersDecember 2012106Controller Common Parts (figure 7‐1)NotePart numbers are shown for recommended spares on

Page 10 - Panel Mounting

Instruction ManualD200160X0124195K ControllersDecember 2012107Key Description Part NumberNoteOne type of pressure gauge is used for both output pressu

Page 11 - Actuator Mounting

Instruction ManualD200160X0124195K ControllersDecember 2012108Key Description62 Remote set pt ass'y (suffix letter M)NoteThe part numbers listed

Page 12 - Pressure Connections

Instruction ManualD200160X0124195K ControllersDecember 2012109Figure 7‐1. Controller Assembly DrawingsSECTION D‐DSEE VIEW H SEE VIEW GBBSEE VIEW LCCDD

Page 13

Instruction ManualD200160X0124195K ControllersDecember 201211Figure 2‐3. Panel MountingHEX HEADCAP SCREW(KEY 66)LOCKWASHER(KEY 67)ROUNDHEADMACHINESCRE

Page 14

Instruction ManualD200160X0124195K ControllersDecember 2012110Figure 7‐1. Controller Assembly Drawings (cont'd)FF F FVIEW F‐F VIEW F‐FVIEW E4195K

Page 15 - Manual Set Point Adjustment

Instruction ManualD200160X0124195K ControllersDecember 2012111Figure 7‐1. Controller Assembly Drawings (cont'd)VIEW F‐FVIEW F‐FVIEW E4195KC CONTR

Page 16 - Changing Controller Action

Instruction ManualD200160X0124195K ControllersDecember 2012112Figure 7‐1. Controller Assembly Drawings (cont'd)SECTION B‐B4195KA CONTROLLERSSECTI

Page 17

Instruction ManualD200160X0124195K ControllersDecember 2012113Figure 7‐1. Controller Assembly Drawings (cont'd)56A9752‐U SHT 456A9752‐U SHT 356A9

Page 18

Instruction ManualD200160X0124195K ControllersDecember 2012114Figure 7‐2. Process and Set Point Indicator Assembly for Bourdon Tube Controllers32B1532

Page 19

Instruction ManualD200160X0124195K ControllersDecember 2012115Figure 7‐3. Process and Set Point Indicator Assembly for Capsular Element Controllers (P

Page 20

Instruction ManualD200160X0124195K ControllersDecember 2012116Key 383* Bourdon TubesBAR RANGE PSIG RANGE PART NUMBERS31600 (316 SST) Bourdon Tube0 to

Page 21

Instruction ManualD200160X0124195K ControllersDecember 2012117Key 61 Process Scale, Positive PressureScale Range Part NumberBar Scales0 to 150 mbar0 t

Page 22 - Flapper Alignment

Instruction ManualD200160X0124195K ControllersDecember 2012118Capsular Element Assembly (key 113)(figure 7‐5)Key Description12 Cap screw, hex socket,

Page 23 - Overall Operation

Instruction ManualD200160X0124195K ControllersDecember 2012119Figure 7‐5. Capsular Element AssemblyVIEW A‐AVIEW A‐AVIEW A‐AVIEW A‐A58A0708‐E58A0710‐CP

Page 24

Instruction ManualD200160X0124195K ControllersDecember 201212Pressure Connections WARNINGTo avoid personal injury or property damage resulting from t

Page 25

Instruction ManualD200160X0124195K ControllersDecember 2012120Figure 7‐6. Remote Set Point Assembly APPLY LUB / SEALANT36A6988‐CKey Description86

Page 26

Instruction ManualD200160X0124195K ControllersDecember 2012121Figure 7‐7. Auto/Manual Station Assembly48A2905‐A APPLY LUB / SEALANTAABBCCSECTION A‐

Page 27 - Rate Adjustment

Instruction ManualD200160X0124195K ControllersDecember 2012122Key Description Part Number298* O‐ring, nitrile 1E222606992299 Rocker, A96061 (aluminum)

Page 28

Instruction ManualD200160X0124195K ControllersDecember 2012123Regulator Mounting PartsDescriptionRegulator Mounting Parts forCasing‐Mounted RegulatorC

Page 29

Instruction ManualD200160X0124195K ControllersDecember 2012124Emerson Process Management Marshalltown, Iowa 50158 USASorocaba, 18087 BrazilChatham, Ke

Page 30

Instruction ManualD200160X0124195K ControllersDecember 201213Use a suitable supply pressure regulator to reduce the supply pressure source to the norm

Page 31

Instruction ManualD200160X0124195K ControllersDecember 201214Vent WARNINGPersonal injury or property damage could result from fire or explosion of ac

Page 32

Instruction ManualD200160X0124195K ControllersDecember 201215Section 3 4195KA Proportional‐Only ControllersAdjustments for 4195KA ControllersThis sect

Page 33

Instruction ManualD200160X0124195K ControllersDecember 201216Remote Set Point (suffix letter M) AdjustmentCAUTIONDo not manually move the set point in

Page 34

Instruction ManualD200160X0124195K ControllersDecember 201217D For reverse control action—An increasing sensed vacuum decreases output pressure.After

Page 35

Instruction ManualD200160X0124195K ControllersDecember 2012187. The controller output pressure should be 0 bar (0 psig).8. Rotate the proportional b

Page 36

Instruction ManualD200160X0124195K ControllersDecember 201219General Calibration InstructionsNoteIf the controller has the auto/manual station (suffix

Page 37

Instruction ManualD200160X0124195K ControllersDecember 20122Contents (continued)Auto/Manual Switching (Option E) 44...Prestartup Checks 44...

Page 38

Instruction ManualD200160X0124195K ControllersDecember 201220Figure 3‐3. Fisher 4195KA Controller Calibration Adjustment LocationsPROCESSPOINTER SPANA

Page 39

Instruction ManualD200160X0124195K ControllersDecember 2012211. Remove the two screws (key 6) and lift off the proportional band indicator cover (key

Page 40

Instruction ManualD200160X0124195K ControllersDecember 2012229. Make sure the set point indicator is within ±1 percent of the mid‐scale mark and if s

Page 41 - External Feedback Operation

Instruction ManualD200160X0124195K ControllersDecember 20122312. Set the proportional band to 400 percent in the desired controller action and replac

Page 42 - Operating Information

Instruction ManualD200160X0124195K ControllersDecember 201224Remote Set Point (suffix letter M) OperationThe capability to adjust the controller set p

Page 43

Instruction ManualD200160X0124195K ControllersDecember 201225Section 4 4195KB Proportional‐Plus‐Reset Controllers and4195KC Proportional‐Plus‐Reset‐Pl

Page 44

Instruction ManualD200160X0124195K ControllersDecember 201226Remote Set Point (suffix letter M) AdjustmentCAUTIONDo not manually move the set point in

Page 45

Instruction ManualD200160X0124195K ControllersDecember 201227Bourdon Tube or Capsular Element Controllers for Positive or Compound PressureD For direc

Page 46 - Setting Switching Points

Instruction ManualD200160X0124195K ControllersDecember 201228To switch from manual to automatic mode, adjust the set point to move the ball into the s

Page 47

Instruction ManualD200160X0124195K ControllersDecember 2012291. Be sure the supply pressure regulator is delivering the proper supply pressure to the

Page 48 - Principle of Operation

Instruction ManualD200160X0124195K ControllersDecember 20123Figure 1-1. Fisher 4195K Gauge Pressure ControllersNAMEPLATEW5663‐1W6831Contents (continue

Page 49

Instruction ManualD200160X0124195K ControllersDecember 201230Calibration of 4195KB and KC Controllers WARNINGTo avoid personal injury or property dam

Page 50 - Auto/Manual Option

Instruction ManualD200160X0124195K ControllersDecember 201231Figure 4‐3. Fisher 4195KB and KC Controller Calibration Adjustment LocationsRATEADJUSTMEN

Page 51 - Section 6 Maintenance

Instruction ManualD200160X0124195K ControllersDecember 2012324. The process pointer should indicate the process scale lower limit. If not, adjust the

Page 52

Instruction ManualD200160X0124195K ControllersDecember 20123310. Loosen the remote set point zero adjustment locking screw and adjust the remote set

Page 53

Instruction ManualD200160X0124195K ControllersDecember 2012349. Set the proportional band between DIRECT and REVERSE.10. The controller output shoul

Page 54

Instruction ManualD200160X0124195K ControllersDecember 20123521. When the flapper is correctly aligned, set the proportional band to 400 percent in t

Page 55

Instruction ManualD200160X0124195K ControllersDecember 201236differential pressure or counterclockwise to increase the differential pressure. The diff

Page 56 - Replacing the Case and Cover

Instruction ManualD200160X0124195K ControllersDecember 201237The input element is connected to the process pointer and to the flapper by connecting li

Page 57 - Replacing the Gauges

Instruction ManualD200160X0124195K ControllersDecember 201238Figure 4‐6. Fisher 4195KC Controller SchematicSET POINTINDICATORPROCESS POINTERREMOTE SET

Page 58 - Assemblies

Instruction ManualD200160X0124195K ControllersDecember 201239A 4195KC controller also has a rate valve as shown in figures 4‐6 and 4‐7. This valve is

Page 59

Instruction ManualD200160X0124195K ControllersDecember 20124Section 1 IntroductionScope of ManualThis instruction manual provides installation, operat

Page 60

Instruction ManualD200160X0124195K ControllersDecember 201240Auto/Manual Station (suffix letter E) OperationA controller with the auto/manual station

Page 61

Instruction ManualD200160X0124195K ControllersDecember 201241External Feedback OperationExternal feedback is available for all 4195KB controllers. Con

Page 62

Instruction ManualD200160X0124195K ControllersDecember 201242Section 5 4195KS Differential Gap ControllersOperating InformationThis section includes d

Page 63

Instruction ManualD200160X0124195K ControllersDecember 201243Figure 5‐1. Fisher 4195KS Controller Parts and Adjustments Locations (continued)C0528‐1SC

Page 64

Instruction ManualD200160X0124195K ControllersDecember 201244The white portion of the adjustment enables direct controller action; the black portion e

Page 65

Instruction ManualD200160X0124195K ControllersDecember 201245If they are used, slowly open the upstream and downstream manual control valves in the pi

Page 66

Instruction ManualD200160X0124195K ControllersDecember 2012461. Refer to figures 5‐1 and 5‐2 for location of adjustments.2. Remove the two screws (k

Page 67

Instruction ManualD200160X0124195K ControllersDecember 201247The controller output signal will not return to zero pressure until decreasing process pr

Page 68

Instruction ManualD200160X0124195K ControllersDecember 2012488. Observe the process pointer when the output switches at the upper switching point. Th

Page 69

Instruction ManualD200160X0124195K ControllersDecember 201249The input element is connected to the process pointer and to the flapper by connecting li

Page 70

Instruction ManualD200160X0124195K ControllersDecember 20125Table 1-1. SpecificationsAvailable ConfigurationsSee table 1-2Input Signal (Process Sensor

Page 71

Instruction ManualD200160X0124195K ControllersDecember 201250Remote Set Point (Option M)The capability to adjust the controller set point from a remot

Page 72

Instruction ManualD200160X0124195K ControllersDecember 201251Section 6 MaintenanceController parts are subject to normal wear and must be inspected an

Page 73 - Replacing the Bourdon Tube

Instruction ManualD200160X0124195K ControllersDecember 201252Table 6‐1. Troubleshooting Chart Fault Possible Cause Check Correction1. Process wanders

Page 74

Instruction ManualD200160X0124195K ControllersDecember 201253Table 6‐1. Troubleshooting Chart (continued)CorrectionCheckPossible CauseFault2. Controll

Page 75

Instruction ManualD200160X0124195K ControllersDecember 201254Table 6‐1. Troubleshooting Chart (continued)CorrectionCheckPossible CauseFault6. Controll

Page 76

Instruction ManualD200160X0124195K ControllersDecember 201255Replacing Common Controller Parts WARNINGTo avoid personal injury or property damage cau

Page 77

Instruction ManualD200160X0124195K ControllersDecember 2012565. Secure the scale with the four self‐tapping screws (key 37).6. If the controller has

Page 78

Instruction ManualD200160X0124195K ControllersDecember 201257CAUTIONThe case and cover are an integral unit; attempting to separate them will damage t

Page 79

Instruction ManualD200160X0124195K ControllersDecember 201258Replacing the Supply Gauge, Proportional, Reset, Reset Valve, and Positive Feedback Tubin

Page 80

Instruction ManualD200160X0124195K ControllersDecember 201259Figure 6‐3. Proportional Band Adjustment and Set Point Beam DetailsE‐RING(KEY 27)RETAININ

Page 81

Instruction ManualD200160X0124195K ControllersDecember 20126Table 1-1. Specifications (continued)HousingDesigned to NEMA 3 (Weatherproof) and IEC 529I

Page 82

Instruction ManualD200160X0124195K ControllersDecember 2012609. Remove the relay nozzle tubing assembly (key 18) from the set point beam assembly (ke

Page 83

Instruction ManualD200160X0124195K ControllersDecember 20126115. Turn the proportional band adjustment knob to 5 percent DIRECT. Refer to figure 6‐6

Page 84

Instruction ManualD200160X0124195K ControllersDecember 20126216. At the frame manifold (key 135), tighten the nut that secures the tubing from the re

Page 85 - Replacing the Process Tubing

Instruction ManualD200160X0124195K ControllersDecember 20126331. Perform the controller calibration procedures and, if necessary, the appropriate rem

Page 86

Instruction ManualD200160X0124195K ControllersDecember 201264Figure 6‐7. Bellows Assembly and Proportional Band Adjustment (Process Scale and Proporti

Page 87

Instruction ManualD200160X0124195K ControllersDecember 20126520. Align flapper leveling screw number 2 with the centerline of the oblong hole in the

Page 88

Instruction ManualD200160X0124195K ControllersDecember 201266Figure 6‐11. Link 2 AdjustmentLEVELINGSCREWNUMBER 11/2 OF PINDIAMETERCONNECTING TAB ONFLA

Page 89 - Precalibration Procedure

Instruction ManualD200160X0124195K ControllersDecember 20126734. Attach link 3 to the set point beam shoe as shown in figure 6‐3.NoteThe following pr

Page 90

Instruction ManualD200160X0124195K ControllersDecember 20126851. Perform the controller calibration procedures and, if necessary, the appropriate rem

Page 91

Instruction ManualD200160X0124195K ControllersDecember 201269CAUTIONWhen removing and replacing the proportional, reset, or positive feedback bellows,

Page 92

Instruction ManualD200160X0124195K ControllersDecember 20127Table 1-3. Process Sensor (Capsular Element) Pressure RatingsCAPSULEMATERIALCAPSULARSTANDA

Page 93

Instruction ManualD200160X0124195K ControllersDecember 20127024. Adjust the reset adjustment to 0.01 minutes per repeat. For a 4195KC controller, set

Page 94

Instruction ManualD200160X0124195K ControllersDecember 2012714. For controllers with anti‐reset windup (suffix letter F), remove the relief valve tub

Page 95 - Replacing the Drive Flexure

Instruction ManualD200160X0124195K ControllersDecember 20127214. For controllers with anti‐reset windup (suffix letter F), insert the relief tubing a

Page 96

Instruction ManualD200160X0124195K ControllersDecember 2012735. Position the controller assembly in the case and start, but do not tighten the nine m

Page 97 - Setting the Travel Stops

Instruction ManualD200160X0124195K ControllersDecember 201274Figure 6‐13. Bourdon Tube Controller LinkLocations and AdjustmentsCOURSE ZERO ADJUSTMENTL

Page 98 - Aligning the Linkage

Instruction ManualD200160X0124195K ControllersDecember 201275the bottom hole (the hole nearest the pointer pivot). If the process pointer has too much

Page 99

Instruction ManualD200160X0124195K ControllersDecember 2012766. Disconnect link 1 from the Bourdon tube and manually position the process pointer to

Page 100 - Assembly

Instruction ManualD200160X0124195K ControllersDecember 20127712. Repeat steps 8 through 11 until leveling screws 1 and 3 protrude an equal distance f

Page 101 - December 2012

Instruction ManualD200160X0124195K ControllersDecember 20127813. Remove the tape from the process pointer and connect link 1 to the Bourdon tube.14.

Page 102

Instruction ManualD200160X0124195K ControllersDecember 201279Figure 6‐18. Bourdon Tube Controller Travel Stop AdjustmentLOWER TRAVEL STOPADJUSTMENT LO

Page 103

Instruction ManualD200160X0124195K ControllersDecember 20128Table 1-4. Process Sensor (Bourdon Tube) Pressure Ratings and MaterialsBOURDON TUBESSPAN(1

Page 104

Instruction ManualD200160X0124195K ControllersDecember 201280NoteAny adjustment of the process pointer span adjustment screw requires readjustment of

Page 105 - Section 7 Parts

Instruction ManualD200160X0124195K ControllersDecember 201281Figure 6‐19. Fisher 4195K Controller Calibration Adjustment LocationsRATEADJUSTMENTRESETA

Page 106

Instruction ManualD200160X0124195K ControllersDecember 20128215. Apply process pressure equal to the mid‐scale value of the process scale span. The p

Page 107

Instruction ManualD200160X0124195K ControllersDecember 201283Replacing Capsular Element Parts WARNINGRefer to the Maintenance WARNING on page 51.CAUT

Page 108

Instruction ManualD200160X0124195K ControllersDecember 201284Figure 6‐20. Cutaway of Long Pivot Clevis AssemblyEND BUSHINGBEARINGSHAFTBEARINGEND BUSHI

Page 109

Instruction ManualD200160X0124195K ControllersDecember 2012852. Remove the tie bar (key 97) from the capsular element assembly by removing the mounti

Page 110

Instruction ManualD200160X0124195K ControllersDecember 201286Figure 6‐21. Capsular Element Controller Link Locations and AdjustmentsLINK 5LINK 1LINK 4

Page 111

Instruction ManualD200160X0124195K ControllersDecember 2012875. Move the set point indicator, manually or with remote set point pressure, to the proc

Page 112

Instruction ManualD200160X0124195K ControllersDecember 201288The controller output must be 0 bar (0 psig). To be sure the controller output is at 0 ba

Page 113

Instruction ManualD200160X0124195K ControllersDecember 201289Precalibration Procedure1. Remove the two machine screws (key 6) and lift off the propor

Page 114

Instruction ManualD200160X0124195K ControllersDecember 20129Section 2 Installation WARNINGTo avoid personal injury or property damage resulting from

Page 115 - With Bourdon tube

Instruction ManualD200160X0124195K ControllersDecember 201290capsule stack. Tighten the travel stop mounting screws to lock it into position. Decrease

Page 116

Instruction ManualD200160X0124195K ControllersDecember 2012915. Loosen the screw on link 5 (key 88) and adjust the link length so that the pivot arms

Page 117

Instruction ManualD200160X0124195K ControllersDecember 201292b. If the pointer indicates greater than the process scale upper limit, rotate the point

Page 118 - Relay (figure 6‐2)

Instruction ManualD200160X0124195K ControllersDecember 201293Use the following procedures to replace the remote set point assembly. Figure 6‐23 shows

Page 119 - (key 62) (figure 7‐6)

Instruction ManualD200160X0124195K ControllersDecember 2012946. Lift out the remote set point assembly by holding the tie bar (key 106), mounting pla

Page 120 - (figure 7‐7)

Instruction ManualD200160X0124195K ControllersDecember 20129510. Apply remote set point pressure equal to 50 percent of the remote set point input ra

Page 121

Instruction ManualD200160X0124195K ControllersDecember 201296shaft in the middle of the bushing end play. Be sure neither bushing is resting against t

Page 122 - Controller Mounting Parts

Instruction ManualD200160X0124195K ControllersDecember 2012971. Remove the two screws (key 6) and lift off the proportional band indicator cover (key

Page 123 - Fittings

Instruction ManualD200160X0124195K ControllersDecember 201298CAUTIONMake sure the loose travel stop nut does not bind on the diaphragm capsule extensi

Page 124

Instruction ManualD200160X0124195K ControllersDecember 2012991. Decrease the remote set point pressure to 0 percent of the remote set point input ran