Monitoring Health of External Solenoid Valve
(SOV) with FIELDVUE™ DVC6200 SIS Digital
Valve Controllers
Contents
Hardware and Software Requirements 2...........
Final Element Pneumatic Tubing Schematics 3......
Configuration Steps 4...........................
Setting up Triggered Profile for SOV Health
Monitoring 4...............................
SOV Health Monitoring Setup 6...................
Determining Pulse Duration Time 7..............
Performing SOV Health Monitoring
while In-Service 8..............................
The FIELDVUE DVC6200 SIS digital valve controller can be used to monitor the capability of the external solenoid valve
to exhaust when it is briefly de-energized (pulse test from the Logic Solver). This is achieved by using the digital valve
controller to monitor the pressure drop on the external SOV when the voltage signal to the SOV is pulsed.
The procedures contained in this Instruction Manual Supplement are to be considered as a guideline only and should
be modified to address site‐specific requirements. Use these procedures in conjunction with the Safety manual
(D103601X012) and Instruction Manual (D103557X012). In addition, exercise good engineering practices and abide
by specific plant safety guidelines for safe operation.
WARNING
This document is not intended to be used as a stand‐alone document. It must be used in conjunction with the following
documents:
Safety Manual for FIELDVUE DVC6200 SIS Digital Valve Controller and Position Monitor (D103601X012)
Fisherr FIELDVUE DVC6200 SIS Instruction Manual (D103557X012) .
Failure to use this instruction manual supplement in conjunction with the above referenced manuals could result in
personal injury or property damage. If you have any questions regarding these instructions or need assistance in obtaining
any of these documents, contact your Emerson Process Management sale office.
Instruction Manual Supplement
D104028X012
DVC6200 SIS
February 2015
Page view 0
1 2 3 4 5 6 7 8 9 10

Summary of Contents

Page 1 - Valve Controllers

www.Fisher.comMonitoring Health of External Solenoid Valve(SOV) with FIELDVUE™ DVC6200 SIS DigitalValve ControllersContentsHardware and Software Requi

Page 2

Instruction Manual SupplementD104028X012DVC6200 SISFebruary 201510Emerson Process Management Marshalltown, Iowa 50158 USASorocaba, 18087 BrazilChatham

Page 3

Instruction Manual SupplementD104028X012DVC6200 SISFebruary 20152Hardware and Software RequirementsThe following equipment is required for testing and

Page 4 - Configuration Steps

Instruction Manual SupplementD104028X012DVC6200 SISFebruary 20153Final Element Pneumatic Tubing SchematicsThe DVC6200 SIS digital valve controller is

Page 5

Instruction Manual SupplementD104028X012DVC6200 SISFebruary 20154Configuration StepsD Ensure that the DVC6200 SIS digital valve controller, with singl

Page 6 - SOV Health Monitoring Setup

Instruction Manual SupplementD104028X012DVC6200 SISFebruary 20155In order to have the DVC6200 SIS record pressure and travel when a SOV pulse test occ

Page 7

Instruction Manual SupplementD104028X012DVC6200 SISFebruary 20156SOV Health Monitoring SetupClear Instrument Buffer as shown in figure 5.Figure 5. Cle

Page 8

Instruction Manual SupplementD104028X012DVC6200 SISFebruary 20157Use the Logic Solver or other external means to briefly de-energize the SOV. For exam

Page 9

Instruction Manual SupplementD104028X012DVC6200 SISFebruary 20158Figure 7. Example of Pulse TestIn this example, only the first pulse test (100ms) is

Page 10 - Instruction Manual Supplement

Instruction Manual SupplementD104028X012DVC6200 SISFebruary 20159Figure 8. Collection VariablesFigure 9 illustrates an example of SOV Health Monitor T

Comments to this Manuals

No comments