Rear Panel Components (Liebert GXT3 230V, 700VA, 1000VA and 1500VA models)
+ 3 External Batteries
Load (%) 700VA 1000VA 1500VA 2000VA 3000VA
10 480 480 339 331 335
20 341 322 225 202 205
30 319 219 184 157 157
40 225 191 154 138 139
50 206 161 139 120 120
60 187 151 123 99 100
70 163 140 105 80 81
80 155 128 93 70 71
90 148 112 79 60 62
100 141 105 71 40 51
Runtime (in minutes)
Internal Battery
Load (%) 700VA 1000VA 1500VA 2000VA 3000VA
10 105 91 75 73 77
20 62 38 35 33 37
30 37 31 22 21 21
40 32 23 16 15 15
50 27 17 11 11 11
60 22 14 10 8 8
70 18 11 6 6 6
80 15 9 5 5 5
90 13 8 4 4 4
100 11 6 4 3 3
+ 1 External Battery
Load (%) 700VA 1000VA 1500VA 2000VA 3000VA
10 307 214 194 166 182
20 183 153 131 121 123
30 150 124 96 79 79
40 131 100 72 41 53
50 109 79 41 38 46
60 98 66 38 34 38
70 81 41 35 30 31
80 72 38 32 25 26
90 63 36 27 21 21
100 41 34 23 17 18
+ 2 External Batteries
Load (%) 700VA 1000VA 1500VA 2000VA 3000VA
10 374 337 310 306 311
20 314 216 185 159 160
30 212 166 148 133 134
40 186 152 126 105 105
50 160 136 103 81 81
60 149 121 83 67 68
70 139 104 72 40 52
80 128 93 62 38 47
90 112 79 40 36 43
100 105 71 38 33 38
+ 4 External Batteries
Load (%) 700VA 1000VA 1500VA 2000VA 3000VA
10 480 480 480 346 480
20 480 340 315 301 303
30 338 316 215 186 187
40 322 220 184 156 156
50 305 198 157 141 141
60 217 166 145 126 127
70 202 158 133 107 108
80 186 149 120 95 97
90 164 141 105 79 81
100 159 133 96 72 73