www.EmersonProcess.com/Bristol Instruction Manual CI-9110 Mar. 2007 Series 9110 Remote Set Regulator Model 9110-00A
0-2 / Contents 9110 Remote Set Regulator SECTION TITLE PAGE # Section 4 - FIELD WIRING (Continued) 4.3 ANALOG VOLTAGE INPUT (1-5 V) WITH
CI-9110 1-1 Introduction Chapter 1 INTRODUCTION 1.1 PRODUCT DESCRIPTION Series 9110-00A, Remote Set Regulators are transducer devices that use an e
Introduction 1-2 CI-5450 Figure 1-1 - Remote Set Regulator The CPU, clock and reset circuitry performs the timing, measurement and decision making
CI-9110 1-3 Introduction Figure 1-2 - Block Diagram of Analog Type Regulator
Introduction 1-4 CI-5450 The feedback pot connects across a regulated +5 Vdc source. The voltage at the feedback pot’s contact corresponds to the mec
CI-9110 1-5 Introduction Figure 1-3 - Block Diagram of Raise/Lower Type Regulator
Introduction 1-6 CI-5450 1.2.4 Raise/Lower Regulator Model A block diagram for the Raise/Lower Regulator model is shown in Figure 1-3. It will be n
CI-9110 1-7 Introduction Table 1A - Model Number Breakdown (Continued) C = PNEUMATIC OUTPUT D = MOUNTING ARRANGEMENT 1 = 3-15 psi 1 = 2 In. P
BLANK PAGE
CI-9110 2-1 Installation Chapter 2 INSTALLATION 2.1 GENERAL Proper installation techniques will ensure highest performance and also minimize measu
IMPORTANT! READ INSTRUCTIONS BEFORE STARTING! Be sure that these instructions are carefully read and understood before any operation is attemp
Installation 2-2 CI-9110 2.3 PRESSURE CONNECTIONS Remote Set Regulators are furnished in models that provide 3-15, 3-27 or 6-30 psig outputs. All m
CI-9110 2-3 Installation shutoff valve allows the supply source to be closed down during maintenance checks without disturbing other equipment operati
Installation 2-4 CI-9110 2.3.3 Line Size For most installations 1/4 inch pipe or tubing is satisfactory. However, if the input or output lines run
CI-9110 2-5 Installation using a flat metal bar or similar tool. When replacing the cover, it should be snugged in and not over-tightened. The threads
BLANK PAGE
CI-9110 3-1 Board Setup Chapter 3 BOARD SETUP 3.1 USING OPTION SWITCHES Two switch assemblies (SW1 and SW2) are used to set options and select ran
Board Setup 3-2 CI-9110 3.1.1 Switch Functions The Regulator assembly is configured by two, eight-switch packages which perform the functions list
CI-9110 3-3 Board Setup 3.3.1 Continuous Signal A continuous input signal is one that, when placed in a TRUE state, will cause the output to change
Board Setup 3-4 CI-9110 The relationship between an ON and OFF pulse time periods are shown by the following two equations: 1) T on Minimum (sec.)
CI-9110 3-5 Board Setup 3.5 GUARD INPUT The guard input (TB1-5 & TB1-6) is used to Enable or Inhibit the command input. This feature provides as
WARRANTY A. Bristol warrants that goods described herein and manufactured by Bristol are free from defects in material and workmanship for one year
Board Setup 3-6 CI-9110 Table 3-3 - Switch SW2 (2-5), Output Rate Of Change SW2-5 SW2-4 SW2-3 SW2-2 Nominal Rate Of Change, ±15% Close Close Clo
CI-9110 3-7 Board Setup FAIL-ZERO MODE (Both Jumpers in B position) In the "B" position (if the Guard signal remains TRUE), a failure of
BLANK PAGE
CI-9110 4-1 Field Wiring Chapter 4 FIELD WIRING 4.1 GENERAL This section illustrates and describes the field wiring terminals and various wiring co
Field Wiring 4-2 CI-9110 Table 4-1 - Terminal Identification For Analog Input Models TERMINAL LEGEND FUNCTION TB1-1 TB1-2 TB1-3 TB1-4 TB1-5 TB1-
CI-9110 4-3 Field Wiring Figure 4-2 - Analog Voltage Input with Guard Figure 4-3 - Analog Current Input with Guard
Field Wiring 4-4 CI-9110 For the application of Figure 4-2, the Carrier Presence output signal of the receiver may be connected to the Guard termina
CI-9110 4-5 Field Wiring Figure 4-5 - Raise/Lower & Guard Inputs from Relay Contacts Figure 4-5 - Raise/Lower & Guard Inputs from Open C
Field Wiring 4-6 CI-9110 CAUTION When using the Regulator with a device that provides latching type outputs (output stays ON until turned OFF), the
CI-9110 4-7 Field Wiring Figure 4-7 - DC Supply Connections 4.8 OPERATING NOTES The startup procedures described herein are general for most appl
How to return material for Repair or Exchange Before a product can be returned to Bristol for repair, upgrade, exchange, or to verify proper operati
Field Wiring 4-8 CI-9110 5. If the output pressure of the Remote Set Regulator fails to change even with a change at the Command input, the intern
CI-9110 5-1 Service Chapter 5 SERVICE 5.1 GENERAL The servicing and calibration procedures described in this section should only be performed by
Service 5-2 CI-9110 5.2 TROUBLESHOOTING HINTS Some basic types of problems that can occur in the field are listed as follows: ○ Unit dead, no moto
CI-9110 5-3 Service 5.3 SETTING OUTPUT LIMITS 5.3.1 General Principles The Regulator provides mechanical output limits that prevent the output fr
Service 5-4 CI-9110 8. Once limits have been set, re-apply dc power and adjust input test circuit (analog or raise/lower) for range value above upper
CI-9110 5-5 Service 5.6 PRELIMINARY CALIBRATION CHECK Once the test setup of Figure 5-2 or 5-3 has been completed, the following conditions must be
Service 5-6 CI-9110 5. If above readings are within stated specifications, stop! No calibration is required. Restore instrument to normal operation.
CI-9110 5-7 Service 2. Reading on test gauge should be minimum range value (3 or 6 psi), ±5%. 3. Adjust input test circuit for 5.000 V. 4. Rea
Service 5-8 CI-9110 5. DMM #1 should read 4.995 V, ±.01 V 6. If the reading of step 5 is out of tolerance, adjust potentiometer R35 on CPU Board t
CI-9110 5-9 Service Figure 5-4 - Assembly, Analog Type CPU Board with Current Output Figure 5-5 - Assembly, Analog Termination Board
Bristol Inc. Repair Authorization Form (off-line completion) (Providing this information will permit Bristol Inc. to effectively and efficiently proce
Service 5-10 CI-9110 Figure 5-6 - Assembly, Raise/Lower Type CPU Board with Current Output Figure 5-7 - Assembly, Raise/Lower Termination Board
CI-9110 6-1 Specifications Chapter 6 SPECIFICATIONS 6.1 ANALOG INPUT MODEL Function: Uses Analog Input to set a pressure output signal. Ranges:
Specifications 6-2 CI-9110 6.3 GUARD INPUT Enables or inhibits command signal input on both Analog and raise/Lower models. 6.4 ANALOG OUTPUT Fun
CI-9110 6-3 Specifications Hysteresis: (Output to gauge) 0.5% of span Motor Protection: Adjustable mechanism limits restrict output for over and un
Specifications 6-4 CI-9110 Humidity: 10 to 95% over -20° to +130° F (-29° to +55° C) range 10 to 50% over +130° to +150° F (+55° to +65° C) rang
CI-9110 7-1 Parts Chapter 7 PARTS 7.1 MODEL 9110 MAIN PARTS Parts Referenced in Figure 7-1 Item Description Part Number 1 Housing 390
Parts 7-2 CI-9111 Figure 7-1 – Remote Set Regulator Actuator Unit
CI-9110 7-3 Parts Parts Referenced in Figure 7-1 (Continued) Item Description Part Number 45 Clamp, Sleeve 390102-01-6 50 #4 Cable Clip
Parts 7-4 CI-9111 7.2 REMOTE SET REGULATOR BASIC PARTS Parts Referenced in Figure 7-3 Item Description Part Number 103 Diaphragm 383825-
Supplement S1400 / 1Supplement S1400Guidelines forSystem Grounding- Contents -IMPORTANCE OF GOOD GROUNDS ... 1GENERAL RECO
Bristol Training GET THE MOST FROM YOUR BRISTOL BABCOCK INSTRUMENT OR SYSTEM • Avoid Delays and problems in getting your system on-line • Minim
2 / Supplement S1400BURRY TO DEPTH OF AT LEAST 3 FEET,DEEPER IN DRY SOIL.(b) INSTALL WITHOUT KINKS OR SHARP BENDS.(a) BRING ALL CONDUCTORS TO THE SU
Supplement S1400 / 3GENERAL RECOMMENDATIONSWhen wiring equipment into a system, the electrical conduit must have a diameter that willaccommodate the d
4 / Supplement S1400GROUND BEDCONDUCTORGROUNDING BUS1" COPPERRADIUS = 12 IN.AWG 4OR LARGERSTRANDED COPPER CABLEAWG 0000AWG 10COPPER WIRESMOOTHLYD
Supplement S1400 / 5the equipment. Wiring from input signal circuits and power circuits should be separatedas much as possible to minimize noise and t
6 / Supplement S1400METER STANDCLAMP OR BRAZECLAMP (S)LIGHTNING &SURGE PROTECTOR#14 BARECOPPER GROUNDCONDUCTORSIGNALCABLECONDUITCLAMPRADIUS = 12 I
Supplement S1400 / 7TYPES OF EARTH GROUNDSA common misconception of a ground is that it consists of nothing more than a metal pipe driveninto the soil
8 / Supplement S1400POWER COMPANY GROUNDAND GROUND RODSERVICETRANSFORMERGROUND BEDCONDUCTORTEST POWER COMPANYGROUND RODLIGHTNINGARRESTERSEACH PHASENOT
Supplement S1400 / 9The ac power required to operate a system typically includes a service transformer located atthe street and a main breaker box and
10 / Supplement S1400increased noise pickup and signal offset errors. If more information is required on this subject,the reader should refer to the p
Supplement S1400 / 11ConduitTrayPwr. GridGroundIsolatedTerminalPower Jumpersfor ground ref.See text.Conduit Pipe*CHASSIS24VRET W1*DPC 33XXMETEL CABINE
A Few Words About Bristol Inc. For over 100 years, Bristol® has been providing innovative solutions for the measurement and control industry. Our pro
12 / Supplement S14001. Multi-Cabinet Instrument Grounding using Multiple Supplies. The instrument ground(24VRET terminal) of each DPC in a cabinet m
Supplement S1400 / 13Equipment Ground Plate BondedTo Structural Steel By Welding,Brazing, Or Bolting Or WithAuxiliary Bond Strap.EquipmentGround Plate
14 / Supplement S1400 4. Setting DPC Power Jumpers. If the DPC is a Model 3335 or 3310, jumpers W1A and W1B onthe System Interconnect Board must be