Emerson 1F98EZ-1421 Specifications Page 5

  • Download
  • Add to my manuals
  • Print
  • Page
    / 8
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 4
5
INSTALLER/CONFIGURATION MENU
Entering and Navigating the Advanced Installer Configuration Menu
On the Home Screen Display, touch the Menu key to display additional key choices. Touch and hold the Installer Config key
for approximately 3 seconds to enter the Thermostat Options Configuration Menu. Touch and hold the Installer Config key
again for approximately 3 seconds to enter the Advanced Installer Configuration Menu.
Ref.
#
Description of
Features in order when
using to choose;
(Use to step back)
Press or Key
to Select Options
Displayed in
Message Area
Displayed in
Clock Digits
(Default) Options
1
Outdoor / Condenser
Configuration AC1 AC0, AC1, AC2, HP1, HP2
CONDENSER
CONFIG
2
Indoor Heat
Configuration GA2 FAN, GA1, GA2, EL1, EL2
INDOOR HEAT
CONFIG
3
B or O terminal
(HP1, HP2 only) O O, b REVERSING VALVE
4 Heat Cycle Rate FA SL, FA HEAT CYCLE RATE
5 Cool Cycle Rate FA SL, FA COOL CYCLE RATE
6
Auxiliary Cycle Rate
(HP1, HP2 only) FA SL, FA
AUXILIARY CYCLE
RATE
7
Energy Management
Recovery On OFF, On
ENERGY MANAGEMENT
RECOVERY
8
Outdoor Remote
Sensor OFF OFF, On OUTDOOR REMOTE SENSOR
9
Auxiliary Off
(HP1, HP2 only) OFF
OFF, 35-80 (in steps of 1 degree)
From OFF, value changes to 80 AUXILIARY OFF
10
Dual Fuel Config
(HP1, HP2 only) 40
OFF, 0 to 50 (in steps of 1 degree)
From OFF, value changes to 40 DUAL FUEL CONFIG
11 Dehumidification OFF
OFF, 40-80 (in 1% steps) - displayed
in the last digits of the Message Area.
From OFF, value changes to 60
DEHUM XX% (where XX
is the DEHUM set point)
12
Independent
Dehumidification OFF OFF, On INDEPENDENT DEHUMID
13 Humidification OFF
OFF, 20-60 (in 1% steps) - displayed
in the last digits of the Message Area.
From OFF, value changes to 40
HUMID XX% (where XX
is the HUM set point)
14
Independent
Humidification OFF OFF, On
INDEPENDENT
HUMID
15 Compressor Lockout OFF OFF, On COMPRESSOR LOCKOUT
Page view 4
1 2 3 4 5 6 7 8

Comments to this Manuals

No comments