Emerson Series 300 H-design User Manual Page 3

  • Download
  • Add to my manuals
  • Print
  • Page
    / 20
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 2
A S CO Series 300 Automatic Transfer Sw itc hes (ATSs) are
Listed under Underwriters Laboratories UL 1008 Standard
for Safety for A u tom atic Transfer Switches . All control
features are UL Component Recognized, which assures that
A S CO autom atic transfer sw itc he s meet OSHA Safety
Requirements and will be acceptab l e to electric al inspec tor s.
ASCO Series 300 Automatic Transfer Switches are suitable
for emergency and standby system applicati ons. They meet
emergency system rating requirements as defined i n
National Electrical Code (NEC) Article 700 and UL 1008.
Also, they are suitable for the require ments of NEC Article
517 Health Care Facilities, NEC Article 701 Legally
Required Standby Systems, NEC Article 702 Optional
Standby Systems, NFPA 99 Health Care Facilities, and
NFPA 110 Emergency and Standby Power Systems.
Rating Label
Eac h autom atic trans fer sw itc h contain s a rating lab el to
define the loads and fault circuit withstand / cl osing ratings.
Refer to the lab el on the transfer switc h for specific values .
Do not exceed the values on the rating label.
Exceeding the rating can cause personal injury
or serious equipment damage.
terminal block TB
for engine start
and switch
position contacts
Transfer
Switch
Controller
power
connections
power
connections
membrane
controls
800 and 1000 amp. size in typical enclosure with location of customer connections
neutral
connections
neutral
connections
Page view 2