Measurable Energy Efciency
Traditional Approach
With Cold Aisle
Containment
With Liebert iCOM and Containment
Compressor
69.7% 50.9% 50.4%
Condensor
9.3% 9.3% 9.3%
Evaporator Fan
21.0% 18.5% 7.2%
Total
100% 78.7% 66.9%
Savings
21% 33%
Traditional Approach
With Cold Aisle
Containment
With Liebert iCOM and Containment
Chiller*
71.3% 64.9% 60%
Pumps*
10.0% 5.4% 5.2%
Air Handler Fan
18.7% 14.3% 7.2%
Total
100% 84.6% 72.4%
Savings
15% 28%
Savings - Direct Expansion System
* Estimated savings based on dedicated data center chiller
Precision
Cooling
62˚F
62˚F
92˚F
67% Fan Speed
IT Racks
IT Racks
97˚F
85˚F
Precision
Cooling
54˚F
54˚F
89˚F
70˚F
75˚F
100% Fan Speed
IT Racks
IT Racks
8
9
8
8
˚
F
7
7
7
0
0
7
7
7
7
7
˚F
˚F
F
Precision
Cooling
62˚F
62˚F
85˚F
90% Fan Speed
IT Racks
IT Racks
94˚F
80˚F
Precision
Cooling
62˚F
62˚F
92˚F
67% Fan Speed
IT Racks
IT Racks
97˚F
85˚F
Precision
Cooling
54˚F
54˚F
89˚F
70˚F
75˚F
100% Fan Speed
IT Racks
IT Racks
8
9
8
8
˚
F
7
7
7
0
0
0
7
7
7
7
7
˚F
˚F
F
Precision
Cooling
62˚F
62˚F
85˚F
90% Fan Speed
IT Racks
IT Racks
94˚F
80˚F
Traditional Operation
With Cold Aisle Containment
Requires less fan power per kW of cooling
Leverages variable fan speed control
Operates with digital scroll technology for
variable capacity control
Provides continuous dynamic adaptation to cooling load
Allows you to easily take advantage of free cooling designs
CMF
67%
62º F
62º F
97º F
97º F
85º F
Precision
Cooling
Liebert
®
Precision Cooling with Liebert iCOM
®
control and Aisle Containment
Savings - Chilled Water System