Operation
17
3.2.2 Compressor Control
All compressorised PEX models operate two (2) stages of cooling. For single compressor models, a hot
gas bypass valve operates in conjunction with the compressor.
Compressor Proportional Bands
Two Single-Step Compressors —Two-Step
First single-step compressor, Cool 1, is started at 50% calculated output from the temperature propor-
tional band, and stopped at 0%. The second compressor, Cool 2, starts at 100% and stops at 50% (see
Figure 13).
One Compressor With Hot Gas Bypass (HGBP) —Two-Step
The compressor and HGBP valve, Cool 1, are started at 50% calculated output from the temperature
propotional band, and stopped at 0%. The HGBP valve de-energises, Cool 2, at 100% and re-energises
at 50%. (see Figure 13).
Figure 13 Two single-step compressors or one compressor with HGBP (two-step)
1/2 Proportional Band
Cool 1
On
Cool 2
On
Cool 1
Off
Cool 2
Off
+ 100%
Cooling
0% 
Cooling
Increasing Temperature
Temp Setpoint: 21
o
C
Proportional Band: 4
o
C
Deadband: 1
o
C
1/2 Deadband
23.52322.52221.521